Appendix F Additional Pdu Information; Default Hysteresis Values For Thresholds; Event Types - Raritan Dominion Px User Manual

Hide thumbs Also See for Dominion Px:
Table of Contents

Advertisement

Appendix F Additional PDU Information

Default Hysteresis Values for Thresholds

Event Types

In This Chapter
Default Hysteresis Values for Thresholds .............................................245
Event Types...........................................................................................245
MAC Address ........................................................................................247
Altitude Correction Factors ....................................................................247
Data for BTU Calculation.......................................................................248
This table describes the default hysteresis values for each type of
measurement. Values must recede past the threshold by the hysteresis
value before the Dominion PX de-asserts the condition. You can disable
the hysteresis feature for outlet current while the feature for other
measurements continue to apply. Or you can change the default
hysteresis on appropriate threshold pages for each measurement.
Measurement
Lower
Critical
Outlet RMS
+0.9
Current (Amps)
Unit/Line RMS
+5
Voltage (Volts)
-
Current (Amps)
-
Current (Amps)
PDU Temperature
+1
(Degrees Celsius)
Environmental
+2
Temperature
(Degrees Celsius)
Environmental
+1
Humidity (%)
Lower
Upper
Non-Critical
Critical
+0.9
-0.9
+5
-5
-
-1
-
-1
+1
-1
+2
-2
+1
-1
Upper
Non-Critical
-0.9
-5
-1
-1
-1
-2
-1
245