Setting Outlet Thresholds And Hysteresis - Raritan Dominion Px User Manual

Hide thumbs Also See for Dominion Px:
Table of Contents

Advertisement

Chapter 5: Using the Web Interface
92
Threshold
Upper non-critical threshold Larger than or equal to the following
Lower non-critical threshold Larger than or equal to the following
4. When you are finished, click Apply.

Setting Outlet Thresholds and Hysteresis

You can set the thresholds for outlet RMS current, and by default, the
Dominion PX assigns a hysteresis value for the outlet threshold.
Note: If you are using a Dominion PX inline monitor, the outlet voltage
threshold and hysteresis are also available on the same page.
To set the current thresholds and hysteresis of an outlet:
1. Choose Details > Outlet Setup. The Outlet Setup page opens.
2. Select an outlet from the "Show setup of outlet" drop-down list.
3. Set the RMS current threshold for the outlet in the Thresholds panel.
Ensure the value you enter for the upper critical threshold is NOT
larger than the maximum current ratings of the outlet.
4. Adjust the hysteresis setting for the outlet threshold if necessary. See
What is Threshold Hysteresis?
the hysteresis.
To disable the hysteresis, type 0 (zero).
To enable the hysteresis, type a non-zero value, which must meet
the rules described in the table:
Threshold
Upper critical threshold
Upper non-critical threshold Larger than or equal to the following
Criterion
formula:
lower non-critical threshold + (2 x
hysteresis)
formula:
lower critical threshold + hysteresis
(on page 142) for the definition of
Criterion
Larger than or equal to the following
formula:
upper non-critical threshold + hysteresis
formula:
lower non-critical threshold + (2 x
hysteresis)