Setting Power Thresholds

6. If disabling an inlet will result in all inlets being disabled, a
confirmation dialog appears, indicating that all inlets will be disabled.
Then click Yes to confirm this operation or No to abort it.
Setting and enabling the thresholds causes the PXE to generate alert
notifications when it detects that any component's power state crosses
the thresholds. See
The Yellow- or Red-Highlighted Sensors
46).
There are four thresholds for each sensor: Lower Critical, Lower Warning,
Upper Warning and Upper Critical.
Upper and Lower Warning thresholds indicate the sensor reading
enters the warning level.
Upper and Lower Critical thresholds indicate the sensor reading
enters the critical level.
To avoid generating a large amount of alert events, you can set the
assertion timeout and deassertion hysteresis.
For detailed information, see
349).
Note: After setting the thresholds, remember to configure event rules.
See
Event Rules and Actions

Setting Inlet Thresholds

You can set the inlet thresholds so that the alerts are generated when
the inlet current and/or voltage crosses the thresholds.
To set the inlet thresholds:
1. Click Inlet I1 in the PX Explorer pane, and the Inlet I1 page opens in
the right pane.
2. Click Setup. The Inlet I1 Setup dialog appears.
3. In the Threshold Configuration table, click the sensor whose
thresholds you want to configure.
4. Click Edit or double-click the desired sensor. A threshold setup
dialog appears.
Chapter 6: Using the Web Interface
Sensor Threshold Settings
(on page 121).
(on page
(on page
119