Rcm Residual Current And State Objects; Setting Rcm Thresholds; Running Rcm Self-Test; Cli Operations For Rcm - Raritan PX3-1000 series User Manual

Px3 series
Hide thumbs Also See for PX3-1000 series:
Table of Contents

Advertisement

CLI Operations for RCM

RCM Residual Current and State Objects

The
inletSensorMeasurementsTable
current and states.
sensorType
Use index
= 26 to retrieve the row for residual current.
measurementsInletSensorValue
Column
sensorType
Use index
= 27 to retrieve the row for RCM state. Column
measurementsInletSensorState
value.

Setting RCM Thresholds

The inletSensorConfigurationTable contains a row for configuring RCM
sensorType
thresholds. Use index
inletSensorUpperWarningThreshold
inletSensorHysteresis
and
deassertion hysteresis respectively.
Note: The PX3 triggers events when residual current values are above
(but not equal to) thresholds. For example, you would set the critical
threshold to 29mA to specify the IEC 62020 IΔn of 30mA. See
Compliance with IEC 62020

Running RCM Self-Test

To initiate RCM self-test using SNMP, set column
table
rcmSelfTestTable
For information on entering and using the CLI, see
Line Interface
(on page 365).
Appendix F: PX3 Models with Residual Current Monitoring
contains entries for RCM residual
contains the residual current.
contains the RCM state enumeration
= 26 to reference the row. Columns
inletSensorUpperCriticalThreshold
,
set values for RCM warning, critical and
(on page 590).
.
rcmState
to value 29 in
Using the Command
599

Advertisement

Table of Contents
loading

This manual is also suitable for:

Px3-2000 series

Table of Contents