Inlet And Outlet Power Connections - Raritan PX3TS Quick Setup Manual

Hide thumbs Also See for PX3TS:
Table of Contents

Advertisement

4. Fasten front mounting ears to the rack using your own
fasteners.
To mount a PX3TS device which is short:
1. Attach a rackmount bracket to both sides of the PX3TS
with the provided screws. For a 1U model, the total
number and locations of screw holes are different from the
following 2U diagram.
2. Insert the cable-support bar into rackmount brackets.
PX3TS Transfer Switch Quick Setup Guide
QSG-PX3TS-0D-v3.1-E  255-80-0032-00 RoHS
3. Secure with the provided end cap screws.
4. On a 2U model, repeat the above steps to install another
cable-support bar.
5. Fasten the rackmount brackets' ears to the rack using your
own fasteners.
QS Rule

Inlet and Outlet Power Connections

The PX3TS connects to two different, but identically rated,
branch circuits.
The PX3TS will operate when the branch circuit voltages are
out of phase, but works most reliably and fastest when in
phase. The front panel Phase Sync lamp lights if inlets are out
of phase.
Connecting Power and Equipment
Your PX3TS may have fuses and/or circuit breakers. Verify
that all are firmly seated or set to ON before connecting
power.
The PX3TS inlets are labeled INLET 1 (I1) and INLET 2 (I2).
INLET 1 is the factory default preferred inlet, and INLET 2 is
the factory default alternate inlet.
Tip: You can switch preferred and alternate inlets if needed.
See
Manual Transfer
(on page 5).
To make power connections:
1. Connect PX3TS inlets to branch circuits.
2. Connect loads to PX3TS outlets.
3. Apply power to branch circuits.
3