I/O Sensors menu

/------------------------/
/
Output
/------------------------/
UPS Lock.......:
Ovrload/Ovrtemp:
UPS Failure....:
On bypass......:
AC Fail........:
Battery low....:
Communic lost..:
Input sensor...:
Press [Esc] to quit
With this menu is possibile to associate a digital output of the installed sensors to one or more
events of the UPS. The output will be closed when the associated event happens.
Press ENTER to select the output.
The identification number is the same which is associated to the sensor during
installation.
The following table describes the meaning of the events. These can vary depending on the UPS
connected.
Event
UPS Lock
Ovrload/Ovrtemp
UPS Failure
On bypass
AC Fail
Battery low
Communic lost
Input Sensor
/
Output
-<--
-
-
-
3
-
-
-NC
Description
UPS is locked
UPS in overload or in overtemperature
Failure of the UPS
Operation from bypass
Operation from battery
Battery low
Communication between the UPS and the device has been interrupted
The state of the input (open/closed) is reported to the output of the
selected sensor.
The digital input monitored is that with the lowest identification number
(the first that was detected during configuration).
It is also possible to select the logic state of the input:
NC: Normally Closed
NO: Normally Open
- 30 -