Top Vent Venting Runs - Montigo B34DV-2 Installation Operation & Maintenance

B-series dv-2
Table of Contents

Advertisement

B-Series DV-2 Gas Fireplace

Top Vent Venting Runs

For the B-Series DV-2 Top Vent, there are two types of installations:
A) Through-The-Wall Installations and B) Vertical (Through-The-Roof)
Installations.
A) Through-The-Wall Installations
Before you install any venting, you must determine whether the venting
run will be acceptable. Unacceptable venting can affect the fireplace's
combustion.
The Venting Graph
Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the from the fireplace flue
collar to the wall flange of the termination. Plot on the Venting Graph
(Fig. 9a) with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
B34DV-2
B34DV-2
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 108" and the horizontal run to
the wall flange of the vent termination is 180", this would be an accept-
able installation.
Example B: (Acceptable Installation)
If the vertical dimension from the hearth is 42" and the horizontal run to
the wall flange of the vent termination is 72", this would be an acceptable
installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 60" and the hori-
zontal run to the wall flange of the vent termination is 144", this would
NOT be an acceptable installation.
Figure 9a. B34-DV-2 Top Vent Venting Graph
Page 6
Installation
B38DV-2
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 84" and the horizontal run to
the wall flange of the vent termination is 36", this would be an acceptable
installation.
Example B: (Acceptable Installation)
If the vertical dimension from the hearth is 90" and the horizontal run to
the wall flange of the vent termination is 126", this would be an acceptable
installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 72" and the
horizontal run to the wall flange of the vent termination is 84", this would
NOT be an acceptable installation.
108
96
84
72
60
48
36
24
12
0
0
Hearth
Figure 9b. B38-DV-2 Top Vent Venting Graph
Available Top Vent Components
The following venting components are available for the B-Series DV-2
Top Vent:
A - Termination
B - Stucco Kits
C - Flex Sections
D - Rigid
Sections
E - Elbows
NOTES: All dimension lengths for vertical or horizontal runs are
measured from centre of the vent pipe. Venting runs must
fall within the limits set by the venting graph (see Figure 7).
B38DV-2
12 24 36 48 60 72 84 96 108
120
Horizontal Run (in.)
4" / 7" Venting
MTO-3 (3" Length)
MTO-3F (3" Length)
MSR (Stucco Frame)
MOSR (Stucco Can)
BSR ( Brick Can)
MFL-1 (12" Section)
MFL-2 (24" Section)
MFL-3 (36" Section)
MFL-4 (48" Section)
MEXT-1 (12" m/f Section)
MEXT-2 (24" m/f Section)
MEXT-3 (36" m/f Section)
MEXT-4 (48" m/f Section)
MEL-90MM (m/m 90° Elbow)
MEL-90FF (f/f 90° Elbow)
MEL-90FM (f/m 90° Elbow)
132
144 156 168 180
Part No. XG0160