Service parameter(s) 78-83
78 Desired temperature for anti-bacteria function
Circuit
I
Set the desired temperature for the anti-bacteria function. The
DHW will be charged daily or once a week at the set temperature
to protect against bacteria. The function is always active on
Mondays from 00:00 and the DHW is charged according to the
period set in line 80.
OFF: The anti-bacteria function is not active.
1 ... 100:
80 Anti-bacteria function period
Circuit
I
Set the period for the anti-bacteria function. When the set time
expires, the anti-bacteria function is stopped.
5 ... 250:
The function is activated in line 78 by setting the desired anti-
bacteria temperature.
83 Daily / weekly anti-bacteria function
Circuit
I
Choose whether the anti-bacteria function is to be active daily or
weekly.
ON:
OFF: The anti-bacteria function is active once a
Setting range
OFF / 1 ... 100 °C
The anti-bacteria function is active at the
desired temperature.
Setting range
5 ... 250 min.
The anti-bacteria function is active for the
set period.
Setting range
ON / OFF
The anti-bacteria function is active once a
day (from 00:00).
week (Mondays from 00:00).
32g
Factory setting
OFF
Factory setting
120 min.
Factory setting
ON
The grey
side of the
ECL Card

Advertisement