Service parameter(s) 45-55
45 DHW charging deactivation time
Circuit
I
If the charging time has reached its maximum (line 44), the
charging is deactivated for the set time.
0:
1 ... 250:
52 Compensation of heat loss in circulation circuit
Circuit
I
Choose to compensate for the heat loss of the circulation circuit.
ON: The circulation circuit is kept warm by the
OFF: The circulation circuit is kept warm by the
54 Activation / deactivation of DHW circulation pump
(P3) at anti-bacteria function
Circuit
I
At anti-bacteria function, the pump can be deactivated
independently of the schedule.
ON: The pump always operates according to
OFF: The pump is deactivated at anti-bacteria
55 Activation / deactivation of DHW circulation pump
(P3) during DHW charging
Circuit
I
At DHW charging, the pump can be deactivated independently of
the schedule.
ON: The pump always operates according to
OFF: The pump is deactivated at DHW charging,
Setting range
0 ... 250 min.
No deactivation time.
When the DHW charging time has reached
its maximum, DHW can only be charged
again when the deactivation time has
expired.
Setting range
ON / OFF
storage tank.
The motorized control valve (M1) is closed.
heat exchanger.
The motorized control valve (M1) is active to
keep the charging temperature constant.
Setting range
ON / OFF
schedule II.
function, independently of the schedule.
Setting range
ON / OFF
schedule II.
independently of the schedule.
32e
Factory setting
0 min.
Factory setting
ON
Factory setting
OFF
Factory setting
OFF
The grey
side of the
ECL Card