CAPACITY COMPENSATION RATE FOR PIPE LENGTH

AND HEIGHT DIFFERENCE
MODEL: AO
G07LLCC, AOG09LLCC
COOLING
Indoor unit is higher
Height difference H
(m)
Indoor unit is lower
HEATING
Indoor unit is higher
Height difference H
(m)
Indoor unit is lower
Indoor unit
Connection pipe
 1 Indoor unit is higher than outdoor unit.
15
Û 1
10
7.5
than outdoor unit.
5
0
-5
Û 2
-7.5
-10
than outdoor unit.
-15
15
Û 1
10
7.5
than outdoor unit.
5
0
-5
Û 2
-7.5
-10
than outdoor unit.
-15
Height difference H
H
Outdoor unit
Pipe length (m)
5
7.5
-
-
-
-
-
0.979
0.992
0.983
1.000
0.991
1.000
0.991
-
0.991
-
-
-
-
Pipe length (m)
5
7.5
-
-
-
-
-
0.961
1.000
0.961
1.000
0.961
0.995
0.956
-
0.954
-
-
-
-
Outdoor unit
Connection pipe
 2 Indoor unit is lower than outdoor unit.
- (02 - 05) -
10
15
-
0.872
0.910
0.961
0.886
0.925
0.965
0.890
0.929
0.969
0.893
0.933
0.976
0.901
0.940
0.976
0.901
0.940
0.976
0.901
0.940
0.976
0.901
0.940
-
0.901
0.940
10
15
-
0.832
0.822
0.917
0.832
0.822
0.917
0.832
0.822
0.917
0.832
0.822
0.917
0.832
0.822
0.912
0.828
0.818
0.910
0.826
0.816
0.908
0.824
0.814
-
0.815
0.805
H
Indoor unit
20
20