Function Details - Fujitsu ASG07LLCC Design & Technical Manual

Table of Contents

Advertisement

FUNCTION DETAILS

Functions
1) Filter sign
2) Room temperature control for cooling
3) Room temperature control for heating
4) Auto restart
5) Remote controller custom code
6) Indoor unit fan control for energy saving for cooling
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Setting description
Standard (400 hours)
Long interval (1000 hours)
Short interval (200 hours)
No indication
2) Room temperature control for cooling
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
Setting description
Slightly lower control
Lower control
Higher control
3) Room temperature control for heating
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
Setting description
Lower control
Slightly higher control
Higher control
Function number
Function number
Standard
Function number
Standard
- (01 - 18) -
(  ... Factory setting)
Setting value
00
01
11
02
03
(  ... Factory setting)
Setting value
00
01
30
02
03
(  ... Factory setting)
Setting value
00
01
31
02
03

Advertisement

Table of Contents
loading

This manual is also suitable for:

Asg12llccAog07llccAog09llccAog12llccAsg09llcc

Table of Contents