Capacity Compensation Rate For Pipe Length And Height Difference; Models: Aou18Rglx, Aou24Rglx, Aou30Rglx, And Aou36Rglx - Fujitsu AOU42RGLX Design & Technical Manual

Hide thumbs Also See for AOU42RGLX:
Table of Contents

Advertisement

6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe
6-1. Models: AOU18RGLX, AOU24RGLX, AOU30RGLX, and
AOU36RGLX
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than outdoor
unit *1
Indoor unit is lower than outdoor
unit *2
HEATING
Indoor unit is higher than outdoor
unit *1
Indoor unit is lower than outdoor
unit *2

6-1. Models: AOU18RGLX, AOU24RGLX, AOU30RGLX, and AOU36RGLX

Height difference H
1
*
H
Outdoor unit
m
ft
16
30
98
20
65
10
32
7.5
24
5
16
0.998 0.992 0.982 0.964 0.952 0.938 0.919
0
0
1.000 1.000 0.989 0.972 0.960 0.945 0.926
-5
-16
1.000 1.000 0.989 0.972 0.960 0.945 0.926
-7.5
-24
-10
-32
-20
-65
-30
-98
m
ft
16
30
98
20
65
10
32
7.5
24
5
16
1.000 1.000 0.999 0.963 0.939 0.922 0.907
0
0
1.000 1.000 0.999 0.963 0.939 0.922 0.907
-5
-16
1.000 0.995 0.995 0.958 0.934 0.917 0.903
-7.5
-24
-10
-32
-20
-65
-30
-98
- 90 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length
5
7.5
10
20
24
32
65
0.941 0.929 0.914 0.896
0.974 0.957 0.944 0.930 0.911
0.988 0.978 0.960 0.948 0.934 0.914
1.000 0.989 0.972 0.960 0.945 0.926
0.989 0.972 0.960 0.945 0.926
0.972 0.960 0.945 0.926
Pipe length
5
7.5
10
20
24
32
65
0.963 0.939 0.922 0.907
0.999 0.963 0.939 0.922 0.907
1.000 0.999 0.963 0.939 0.922 0.907
0.983 0.992 0.955 0.932 0.915 0.900
0.990 0.953 0.929 0.912 0.898
0.943 0.920 0.903 0.889

6. Capacity compensation rate for pipe length and height difference

2
*
30
40
50
98
131
164
0.913 0.899 0.881
0.960 0.945 0.926
30
40
50
98
131
164
0.939 0.922 0.907
0.911 0.894 0.880