G
E
T
2.9.8
LINKS Answer
The LINKS Answer zone is only required for downloading to the panel via the LINKS.
When using the LINKS, Busy Tone Detection must not be used.
Keypad zones cannot be used for 24 Hour Supervisory or LINKS Answer.
2.10

Keypad Zones

Keypads with zone inputs can be connected to devices such as door contacts. This saves you from
running wires back to the control panel for every device.
To install the keypad, open the keypad plastic by removing the screw at the bottom of the unit. Locate the
five terminals on the keypad circuit board. Connect the four Keybus wires from the control panel: the red
wire to R, the black to B, the yellow to Y and the green to G.
To connect the zone, run one wire to the Z terminal and the other to B. For powered devices, use red and
black to supply power to the device. Run the red wire to the R (positive) terminal and the black wire to the
B (negative) terminal.
When using end of line supervision, connect the zone according to one of the configurations outlined in Section
2.8 "Zone Wiring." End of line resistors must be placed on the device end of the loop, not at the keypad.
Keypad zones do not support DEOL resistors.
Assigning Keypad Zones
When using keypad zone inputs, each input used must be assigned a zone number in Installer's Programming.
First, ensure that you have enrolled all installed keypads into the desired slots. ( See Section 2.6 "Keypad
Assignment").
Next, enter programming section [020] to assign the zones. There are eight programming locations in this
section, one for each keypad slot. Enter a 2-digit zone number for each of the keypad zones. This number
must be entered in the location corresponding to the keypad to which each zone is connected.
If a keypad zone input is assigned on zone number form 1 to 8, the corresponding zone cannot be
used on the main control panel.
Once the keypad zones are assigned, you must also program zone definitions and zone attributes.
(See also Section 5.1.1 "Assigning Keypad Zones").
T
I
N
G
If the LINKS1000 cellular communicator is being used a zone may be
configured for LINKS Answer to allow downloading to be performed in the
event of phone line failure.
When the LINKS receives a phone call it will activate the RING terminal on the
LINKS circuit board. This terminal can be used to violate a zone programmed
as LINKS Answer (See Section 5.1 "Zone Definitions") , causing the panel to
seize the phone line and begin communication with the downloading
computer.
The zone programmed as LINKS Answer ALWAYS requires a single EOL resistor
(5600Ω) and must be wired according to this diagram.
S
T
A
12
R
T
E
D