System inspection and maintenance

13.1

General information

Offer your customer a maintenance contract covering annual inspection
and servicing work as required. To find out what a contract for annual
inspection and demand-based servicing covers, refer to Chapter 13.7,
page 42.
DANGER: Risk of fatal injury from the explosion of
flammable gases.
▶ Work on gas components must be carried out by
trained and certified personnel only.
Cleaning and maintenance:
If heating oil is being used, cleaning and maintenance must be carried
out twice a year. Depending on demand/run time, a shorter cleaning
interval may be necessary.
Spare parts can be ordered from the Buderus spare
parts catalog.
13.2

Why is regular maintenance important?

You should have your customer's system serviced for the following
reasons:
• to achieve a high level of efficiency and to operate the system
economically (low fuel consumption),
• to achieve a high level of operational safety and reliability
• to maintain a clean and environmentally-friendly combustion.
13.3

Cleaning the boiler with cleaning brushes

▶ Put the main power switch ( Fig. 70, [1]) on the control panel in
position "0".
▶ Shut off the fuel supply to the burner.
▶ De-energize the system.
1
Fig. 70 Logamatic 4311 shown as an example
▶ Undo the four machine screws that fasten the burner door to the
front section ( Fig. 71, [1 to 4]).
▶ Swing out burner door.
Logano G515 – 6 720 647 208 (2014/09)
4
3
Fig. 71 Fastening the burner door
▶ Remove the flue gas baffles from the flue gas passages ( Fig. 72,
[1 to 4]).
4
3
2
Fig. 72 Flue gas baffles, removing
The various brush types available from Buderus (accessories) are shown
6 720 642 623-73.1O
in Fig. 73.
System inspection and maintenance
Boilers rated at 510 with 12 boiler sections are not
equipped with flue gas baffle plates. Flue gas baffle
plates are not used in boilers rated between 240 – 455
with 7 – 11 boiler sections ( Chapter 7.8.5,
page 22).