Designated Use; Operating Conditions; Compliance With Standards And Regulations - Buderus Logano G515 Installation And Service Instructions Manual

Low-temperature oil/gas boiler buderus logano g515
Hide thumbs Also See for Logano G515:
Table of Contents

Advertisement

2
Product description
2.1

Designated use

The Logano G515 oil/gas-fired boilers have been designed for the
heating of water.
The Logano G515 can be operated with oil, gas, and combination
burners. For a list of the approved burners, please contact Bosch
Thermotechnology Corp.
This boiler can be operated with an aquastat, the Logamatic 4000, and
other control systems.
Minimum flow rate
Minimum return temperature
Minimum operating temperature oil boiler
Minimum operating temperature gas boiler
Maximum supply temperature
Maximum operating pressure
Time constant of the temperature controller
Time constant of the monitor/limiter
Table 3
1) This temperature has to be reached within ten minutes of the burner starting and has to be maintained whilst the burner is firing.
2) The maximum supply temperature is 212 °F (100 °C), if the boiler is operated as hot water boiler.
3) The maximum supply temperature is 248 °F (120 °C), if the boiler is operated as a hot water generator.
This operating condition can be easily achieved by the controls
monitoring the boiler temperature and reducing the flow rate through
the boiler until the required temperature is reached. This is then
maintained by continuing to control flow based on the boiler water
temperature. The controls can reduce the flow rate by closing the valves
on the mixed heating circuits, modulating the boiler primary pumps or by
closing the motorized butterfly valves or by having a motorized valve in
the boiler return on a single boiler installation. The Buderus 4000 series
control panel can manage this process or it can be completed by the
BMS.
If it is not possible for the control panel to regulate the flow sufficiently to
meet this operating condition, then a shunt pump circuit must be fitted
to avoid the type of thermal stress that all boilers would experience in
these conditions. This shunt pump circuit can be controlled either with a
Buderus 4000 control panel or with a third-party controller. Failure to
ensure that the operating condition is maintained may lead to thermal
stress in the boiler and eventual failure of the sections which would be
outside the scope of the warranty.
6
°F ( °C)
1)
°F ( °C)
1)
°F ( °C)
°F ( °C)
PSI (bar)
sec
sec
2.2

Operating conditions

Thermostream technology is a unique feature of Buderus cast iron
boilers. Return water is preheated and mixed within the boiler before it
comes in contact with the heating surface of the combustion chamber.
The Thermostream technology ensures there is an even temperature
distribution in the boiler and avoids condensate forming within the
combustion chamber. This unique feature reduces thermal stress, the
main cause of failure of traditional cast iron boilers. The advantage of
this technology is the maintenance of the minimum operating
temperature of the boiler ( Tab. 3); this makes the installation of a
shunt pump unnecessary. This way, the costs for the pump itself and its
power consumption, as well as possible failure costs are saved. The
minimum boiler operating temperature as shown in the table below must
be reached within 10 minutes and then be maintained while the burner
is running.
Control of all heating zones
with Buderus 4000
122 (50)
122 (50)
2)
212
/248
2.3

Compliance with standards and regulations

Installation and operation of the system must comply with all applicable
codes, regulations and statutory requirements.
Installation, connection of the fuel supply and flue connector,
commissioning, connection of the electrical power supply, servicing and
repair may only be carried out by trained and certified heating
contractor. Only registered gas fitters may carry out work on the gas
train.
The system must be cleaned and serviced once a year. The operation of
the complete system must be tested at the same time. Any faults must be
corrected immediately.
The design and mode of operation of this boiler comply with the
American National Standard ANSI Z21.13/CSA4.9, latest edition for
Gas Fired Low Pressure Steam and Hot Water Boilers.
Other confirmed approvals and certifications are indicated by labels on
the boiler.
The heat exchanger has been designed and certified in accordance with
the ASME Boiler and Vessel Code, Section IV.
External controls (BMS)
or Aquastat control
none
none
140 (60)
3)
2)
3)
(100
/120
)
87 (6)
40
40
Logano G515 – 6 720 647 208 (2014/09)