Danfoss DHP-H Installation And Service Instructions Manual page 62

Table of Contents

Advertisement

Menyval
MAX TEMP.
START HGW
INITIALIZING HGW
INTEGRAL DELAY
HGW-SHUNT TIME
HGW INT. BOUND.
HGW INTEGRAL
PULSE WIDTH
PULSES
62
Betydelse
Max temperature of the water in the water heater. The temperature is measured
on the peak sensor in the water heater.
NOTE! Domestic hot water can have this temperature, which can mean that an
external mixer valve may be required.
The number of seconds the HGW shunt is to open at HGW start is the starting
point of shunt opening.
The opening time for the HGW shunt from fully closed to fully open towards the
water heater is 30 seconds.
The time in seconds before control of HGW shunt starts after HGW start.
Delay of integral calculation in seconds after the integral value for HGW has
been reached.
The time that the signal is active to open or close the HGW shunt completely.
Integral value (parameter) for HGW.
Shows the actual value for the HGW integral. Plus indicates that the shunt opens
towards the hot water heater and minus indicates that the shunt opens towards
the heating system.
How long the plus or minus signal to the shunt is to be high when the HGW inte-
gral has been reached.
Shows the relevant position for the shunt from the starting point for START HGW.
At start-up the value is zero and for each + pulse that is sent to the sensor, the
value goes up one step. For - pulse, the value goes down one step.
VMBMA602
Fabriksinställning
95°C
(interval: 60°C / 100°C)
7S
(interval: 0S / 30S)
60S
(interval: 10S / 90S)
10S
(interval: 5S / 120S)
35S
(interval: 15S / 60S)
60 (interval: 10 / 120)
-
0,25S
(interval: 0,20S / 1,00S)
-