Toshiba RAV-SM560AT-E Service Manual page 151

Toshiba hfc r410a split type air conditioners service manual
Hide thumbs Also See for RAV-SM560AT-E:
Table of Contents

Advertisement

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[Mounting]
1. As same as P .C. board before replacement, attach a cable (Black) which is screwed to the electric parts
box to CN240 without using a cable (Black) attached previously to CN240 of the service P .C. board.
2. Attach other cables as same as P .C. board before replacement.
<(Reference) Explanation about functions of switches/jumpers>
• The following table shows the functions of the main switches and jumpers. Use as reference in miss-setup.
Part name
TA shift: Thermo-OFF point can be shifted in heating operation.
1
SW03
2
Selection of hot start control temperature :
The starting temperature of the fan can be raised in heating operation.
J09
Setup of filter timer
J11
J12
In case of AIK-PXXXH series
Service P.C. board
Bit 1
Bit 2
OFF
OFF
+ 6K
OFF
ON
+ 4K
ON
OFF
+ 2K (Setup at shipment)
ON
ON
± 0K
J09
Provided
Normal (Setup at shipment)
None
Fan starting temp up (Approx. +4K)
J11
J12
Provided
Provided
240 hours (Setup at shipment)
None
Provided
2500 hours
Provided
None
5000 hours
None
None
Without filter timer
www.ilmalämpöpumput.com
CN204
Cable
(Remove a cable
attached previously
to CN240 of the
service P.C. board.)
Function
Shift Q'ty
Setup
Setup