Toshiba RAV-SM560AT-E Service Manual page 114

Toshiba hfc r410a split type air conditioners service manual
Hide thumbs Also See for RAV-SM560AT-E:
Table of Contents

Advertisement

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
2. Reading of CHECK monitor display
<7 segment display>
0
1
2
3
<Display on CHECK monitor>
CHECK code
<FILTER data>
(Example)
Case that Filter signal is sent from No.1 and No.16 units under group operation
<CHECK data>
(Example)
Room temp.sensor of No.1 is defective.
In No.16, first the heat exchanger sensor has failed.
Next, interconnection wire (serial signal line) of indoor/outdoor is defective.
CHECK
UNIT
1
(Example) There is no check data.
CHECK
4
5
6
7
8
CHECK
1 2
UNIT
FILTER
CHECK
1
www.ilmalämpöpumput.com
9
10
11
12
13
UNIT
FILTER
UNIT
– 114 –
Hexadecimal
notation
Decimal notation
14
15
FILTER sign
Indoor unit No.
UNIT
FILTER
CHECK
UNIT
2