Toshiba RAV-SM560AT-E Service Manual page 119

Toshiba hfc r410a split type air conditioners service manual
Hide thumbs Also See for RAV-SM560AT-E:
Table of Contents

Advertisement

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
Operation of diagnostic function
Block
Check
display
code
[MODE] lamp
Error in indoor fan system
5Hz flash
Revolutions frequency error of
fan
Error in indoor unit or other
positions
1. EEPROM access error
Outside error input
Detected by input voltage level
from outside devices
Outside interlock input
Detected by input voltage level
from outside devices
Operation of diagnostic function
Check
Cause of operation
code
Serial return signal is not sent
from No. 1 indoor unit to
remote controller.
• Miscabling of inter-unit cable
between remote controller
and indoor unit
• Miss-setting of indoor unit No.
(Group address)
Error mode detected by indoor unit (1)
Status of air
Cause of operation
conditioner
All stop
Operation
continues
Operation
continues
All stop
Error mode detected by indoor unit (2)
Status of air
Condition
conditioner
ON/OFF
Displayed when
error is detected
– 119 –
www.ilmalämpöpumput.com
Judgment and measures
Condition
Displayed when
1. Check indoor fan motor connector
error is detected
circuit (CN210).
2. Check indoor fan.
3. Check indoor P.C. board (Main P.C.
board).
Displayed when
1. Check indoor P.C. board
error is detected
(EEPROM and peripheral circuits)
(Main P.C. board).
Displayed when
1. Check outside devices.
error is detected
2. Check indoor P.C. board (Main P.C.
board).
Displayed when
error is detected
Judgment and measures
1. Indoor unit does not completely operate.
• Check inter-unit cable.
• Check indoor P .C. board. (Main/Sub P.C. boards)
• Check remote controller.
2. In normal operation
• Check setting of indoor unit No.
(SW01) (Sub P .C. board)
• Check remote controller.