Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

1-2. Outdoor Unit

Model name
Appearance
Power supply
Type
Compressor
Motor
Pole
Refrigerant charged
Refrigerant control
Standard length
Max. total length
Pipe
Over 20m
Height difference
Height
Outer
Width
dimension
Depth
Total weight
Heat exchanger
Fan
Fan unit
Standard air flow High
Motor
Gas side
Connecting
pipe
Liquid side
Protection device
Sound level
High (Mid./Low)
(Note 2)
(Cooling/Heating)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping. The reference piping consists of 3 m piping connected with 0 meter height.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note
: Rated conditions
(kW)
(kg)
(m)
Outdoor lower
(m)
Outdoor higher
(m)
(mm)
(mm)
(mm)
(kg)
(m³/h)
(W)
(mm)
(mm)
(dB•A)
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
www.ilmalämpöpumput.com
RAV-SM560AT-E
Silky shade (Muncel 1Y8.5/0.5)
1 phase 230V (220 – 240V) 50Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
1.1
R410A 0.9
Pulse motor valve
20 (without additional charge)
30
Add 20g/m (Max. 200g)
595
780
270
35
Finned tube
Propeller fan
2400
43
Ø12.7 (1/2")
Ø6.4 (1/4")
Discharge temp. sensor
Over-current sensor
Compressor thermo.
46/48
– 11 –
RAV-SM800AT-E
1.6
4 poles
R410A 1.5
50
Add 40g/m (Max. 1200g)
30
50
795
780
270
55
3400
63
Ø15.9 (5/8")
Ø9.5 (3/8")
45/50