Before You Begin; General Requirements; Mounting Requirements; Cable Requirements - American Dynamics SpeedDome RASEL Series Installation And Service Manual

Speeddome optima lt indoor camera dome
Table of Contents

Advertisement

Before You Begin

To ensure a smooth and successful installation,
observe the following requirements.

General Requirements

· Have electrical work comply with latest national
electrical code, national fire code, and all
applicable local codes and ordinances.
· Coordinate work with other trades to avoid
interference.
· Verify existing site conditions and coordinate
with the owner's representative and appropriate
utilities as required.
· Obtain copies of all related plans, specifications,
shop drawings and addenda to schedule and
coordinate related work.
· Thoroughly review the project to ensure that all
work meets or exceeds the above requirements.
Bring alleged discrepancies to the attention of
the CCTV Project Coordinator.

Mounting Requirements

Mounting space: Ensure there is the following
space above the ceiling to accommodate the
dome.
Height above ceiling:
170mm (6.7in)
Diameter: 192mm (7.5in)
Structural members: Verify that ceiling members
can support the camera dome and mounting
structure, if used.
Weight: 2.5kg (5.5 lbs)

Cable Requirements

Data cables: The following table shows cable
requirements for SensorNet and Manchester
networks. For more information about
communication protocols and cable networks, see
Communication Protocols and Cable Networks,
8000-2573-19.
SPEEDDOME OPTIMA LT INDOOR CAMERA DOME INSTALLATION AND SERVICE GUIDE (8200-0181-01, REV. C)
Data cable requirements
SensorNet
Cable type
1
unshielded,
twisted
pair*
Wire gauge
22 AWG
Non-
Connection
polarized
Max.
32
devices per
cable run
* Power, data, and video cables can be ordered
separately or within a composite cable that can be
ordered in various lengths. Plenum-rated cables must
be used in indoor ceilings used for environmental air
return (called "other air space" in the National
Electrical Code). Order parts through your distribution
network.
Note: If you order cable from an outside source, wire
colors may be different.
** Belden 88760 (plenum), or Belden 8760 cable (non-
plenum) cable is recommended. Plenum-rated cables
must be used in indoor ceilings used for environmental
air return (called "other air space" in
Electrical Code). Order cable directly from
Belden by calling 1-800-235-3361.
Plenum ceilings: Cable must be rated for plenum
or routed through flexible conduit. A cover plate for
the dome accepts ½" conduit.
WARNING!
!
to or in the same conduit as line voltage
mains power.
Power cables. Make power cable lengths as short
as possible to minimize the affects of low line
voltages and outdoor cold temperature perform-
ance. Maximum cable length between a Class 2
LPS (low voltage) ac source, such as a J-box, and
the dome depends on the ac line voltage. See the
tables below for maximum cable lengths based on
the worst-case low line voltages.
The line voltage must not go below the voltage
shown for the dome to be able to power up and
operate at the corresponding distances shown.
Typically cable distances are used that provide a
15% margin between nominal and low line
conditions. For example, if the nominal voltage
measures 120Vac, restrict the cable length to the
distance for .85 x 120 or approximately 100Vac.
3 of 14
Manchester
1
shielded
twisted
pair**
18 AWG
Polarized
3
the National
Do not run cables adjacent

Advertisement

Table of Contents
loading

Table of Contents