BLOWER SPEED CONTROL – SUF 119300 THRU 119500
The CCB monitors a feedback signal from a sensor that is installed on the blower. The CCB interprets the
pulse signal from the sensor and then sends a signal to the variable frequency drive (VFD) which in turn
transmits the proper frequency to the blower to produce the proper blower speed and input. Refer to the
Variable Frequency Drive on next page for its operation.
Below is a chart for the blower rpms and corresponding VFD Hertz Readings for those rpms displayed on
the VFD.
Note: These models are capable of modulating their input rate. Therefore, the RPM readings can be in
between the Heating Speed and Minimum Modulation Speed RPMs. The input rate should be verified
with the water heater operating at full input rate.
Model
SUF 119300 Nat
SUF 119300 LP
SUF 119400 Nat
SUF 119400 LP
SUF 119500 Nat
SUF 119500 LP
40
Heating
Heating
Speed
Speed
RPM
VFD Hertz
Reading
3450
117.4
3200
108.8
4625
158.3
4200
143.2
5750
198.2
5225
179.8
Servicing should only be performed by a Qualified Service Technician
Minimum
Minimum
Modulation
Modulation
RPM
VFD Hertz
Reading
2350
79.7
2310
78.5
2350
79.7
2310
78.5
2350
79.7
2310
78.6
Ignition
Ignition
Speed
Speed
RPM
VFD Hertz
Reading
4500
153.8
5770
198.2
4500
153.8
5770
198.2
4500
153.8
5770
198.2