Blower Speed Control Suf 199 And 250 - State Water Heaters SUF60 Service Handbook

Commercial gas high efficiency water heaters series 100, 101 and 104.
Table of Contents

Advertisement

BLOWER SPEED CONTROL SUF 199 AND 250

The input of the SUF 199 and SUF 250 is determined by blower. The input of the water heater may be
determined by clocking the meter as shown on Page 5 or by making sure the blower is receiving the proper
signal. The blower rpm is controlled by the Central Control Board (CCB). The rpm of the blower may be
measured by attaching a MULTIMETER that has a Hertz (Hz) setting as shown in the illustration below. If
the Hz signal is within +/-5% of the numbers in the chart below the reading is normal.
199 Propane (LP)
250 Propane (LP)
Note: Removing the plug shown in the illustration will cause the blower to accelerate and the input of the
water heater to increase to a much higher rate. This may cause damage to the water heater.
Meter black lead is connected to ground (not shown) and the red lead is connected to an open terminal on
blower speed control connection.
Model
199 N
250 N
Meter red probe
connected to open
terminal on plug
Servicing should only be performed by a Qualified Service Technician
High Speed Hz
182
227
200
254
Low Speed Hz
172
178
194
191
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Suf 120Suf 100Suf 250Suf 130Suf 500

Table of Contents