BLOWER SPEED CONTROL

The CCB monitors a feedback signal from a sensor that is installed on the blower. The CCB interprets the
pulse signal from the sensor and then sends a signal to the blower to produce the proper blower speed and
input.
Below is a chart for the blower rpms.
Note: These models are capable of modulating their input rate. Therefore, the RPM readings can be in
between the Heating Speed and Minimum Modulation Speed RPMs. The input rate should be verified
with the water heater operating at full input rate.
HEATING SPEED- RPM
NATURAL GAS
*RANGE
SUF 60120
5265-6435
SUF 100150
4815-5885
SUF 100199
6480-7920
SUF 100250
8145-9955
SUF 119300
3105-3795
SUF 119400
4163-5088
SUF 119500
5220-6380
HEATING SPEED- RPM
PROPANE GAS
*RANGE
SUF 60120
5940-7260
SUF 100150
4613-5638
SUF 100199
6188-7563
SUF 100250
7740-9460
SUF 119300
3150-3850
SUF 119400
4050-4950
SUF 119500
5085-6215
*Note: ±10% Heating Speed RPMs are based from the Nominal "Certification" Heating Speed RPMs.
MXI Series 300/301
Production
5460
5185
6880
8700
3450
4625
5750
Production
6060
4992
6550
8230
3200
4200
5225
Servicing should only be performed by a Qualified Service Technician
LOW FIRE
IGNITION SPEED
SPEED RPM
RPM
3220
3500
2725
3000
2725
3000
2725
3000
2350
4500
2350
4500
2350
4500
LOW FIRE
IGNITION SPEED
SPEED RPM
RPM
3750
3000
2625
5100
2625
5100
2625
5100
2310
5770
2310
5770
2310
5770
CONDENSATE
CONDENSATE
SPEED RPM
SPEED TEMP
5460
80°F
5185
90°F
5185
90°F
5185
90°F
3450
80°F
3450
80°F
3450
80°F
CONDENSATE
CONDENSATE
SPEED RPM
SPEED TEMP
6060
80°F
4992
90°F
4992
90°F
4992
90°F
3200
80°F
3200
80°F
3200
80°F
39