Setting The Time Program For Dhw Heating - Viessmann Vitotronic 300-K Operating Instructions Manual

Vitotronic 200, type h01b digital boiler control unit vitotronic 300-k, type mw2b weather-compensated, digital cascade control unit
Table of Contents

Advertisement

Vitotronic 200 and 300-K Operating

Setting the Time Program for DHW Heating

H The time program for DHW heating is made up of time
phases. One time phase from 5:30 to 22:00 h for every
day of the week is set at the factory.
H Automatic mode is set at the factory for DHW heating.
This means that, in standard heating mode, the DHW
is reheated to the set temperature. To ensure that hot
water is available at the start of standard heating mode,
the time phase for DHW heating begins automatically
half an hour earlier than the time phase for standard
heating mode.
H If you don't want the automatic mode, you can select
up to 4 individual time phases per day for DHW heating,
which can be the same for every day of the week or
different. Set the start and end points for each time
phase.
H When setting, bear in mind that your heating system
requires some time to heat the DHW to the required
temperature.
H In the "Extended menu", you can scan the current time
program under "Information" (see chapter "Scanning
information", "DHW" group).
Extended Menu
1.
2. "DHW"
3. "DHW time prog"
4. "Individual"
5. Select part of the week or a day.
6. Select the time phase !, ?, § or $.
7. Set the start and end points for the relevant time
phase.
8. Press
to exit the menu.
Note: If you want to terminate a time phase setting
process prematurely, keep pressing until the
required display appears.
Example shown:
H Time program for Monday to Friday
("Mo-Fr")
H Time phase !:
From 04:30 to 06:30 h
H Time phase ?:
From 15:30 to 20:30 h
Example:
You want to set the same time program for every day
except Monday:
Select the period "Monday–Sunday" and set the time
program.
Then select "Monday" and set the time program for this.
Deleting a time phase
Set the time for the end point to the same time that was
set for the start point. The display shows the selected
time phase "- - : - -".
DHW heating once, no longer in the time program
Note: The heating program "Heating and DHW" or "Only
DHW" must be set for at least one system heating
circuit.
Extended menu
1.
2. "Heating"
3. "Party mode"
4. Disable "Party mode" again with "OFF" to prevent
unintentional central heating with standard room
temperature.
DHW Heating