Hot-Plug System Fans - Compaq ProLiant ML570 Maintenance And Service Manual

Hide thumbs Also See for ProLiant ML570:
Table of Contents

Advertisement

2-14 Compaq ProLiant ML570 Maintenance and Service Guide

Hot-Plug System Fans

The ProLiant ML570 server fans are housed in two system fan baskets. Each basket holds a
primary and a redundant hot-plug system fan. The hot-plug system fans cool the system board
components (I/O fans) and the processors (CPU fans).
To remove a hot-plug system fan:
1. Perform the preparation procedures. See "Preparation Procedures" earlier in this chapter.
2. Remove the access panel. See "Access Panel (Tower and Rack)" earlier in this chapter.
3. Press and hold the locking latches
fan basket.
Figure 2-7. Removing a hot-plug system fan
Reverse steps 1 through 3 to replace a hot-plug system fan.
CAUTION: Never remove BOTH fans from the system fan baskets while the server is powered
up. Overheating and damage to hardware could result. If the appropriate Compaq software
drivers are installed, the operating system software initiates a power shutdown in case of
overheating.
, then lift the hot-plug system fan

2
1
out of the system