6. Specifications

MODEL
CAPACITY*
INPUT
Low Line Loss
Voltage
Low Line Comeback
Range
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Line
Battery
Transfer
Inverter
Bypass
Time
Inverter
ECO
EFFICIENCY
AC mode
Battery Mode
BATTERY
Type & Numbers
Standard
Recharge Time
Model
Charging Current
Charging Voltage
Type
Numbers
Long-run
Model
Charging Current
Charging Voltage
PHYSICAL
Dimension,
Standard
DXWXH(mm)
Model
Net Weight (kgs)
Dimension,
Long-run
DXWXH(mm)
Model
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.
6K
6000 VA / 4800 W
110 VAC ± 3 % at 50% Load; 176 VAC ± 3 % at 100% Load
100%~110%: 10min、110%~130%: 1min、>130% : 1sec
100%~110%: 30sec、110%~130%: 10sec、>130% : 1sec
≦ 3 % @ 100% Linear Load; ≦ 6 % @ 100% Non-linear Load
12 V / 7 Ah x 20
7 hours recover to
3 hours recover to 90%
90% capacity
1 A ± 10% (max.)
4 A ± 10% (max.)
UPS unit: 580X438X133
592X250X576
Battery pack: 580X438
81
592 X250 X576
25
0 ~ 40°C (the battery life will down when > 25°C)
Less than 55dB @ 1 Meter
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Power management from SNMP manager and web browser
6KR
Low Line Loss Voltage + 10V
300 VAC ± 3 %
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Single phase with ground
≧ 0.99 at 100% Load
208/220/230/240VAC
± 1%
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
3:1 max
0 ms
0 ms
<10 ms
> 89%
> 88%
9 hours recover to
capacity
2 A ± 10% (max.)
1 A ± 10% (max.)
14.4 V ± 1%
Depending on applications
18 - 20
2 A ± 10% (max.)
4 A ± 10% (max.)
14.4 V ± 1%
592 X250 X576
X133
UPS unit: 17
Battery pack: 57
580 X 438 X 133
592 X250 X576
17
<95 % and non-condensing
<1000m
29
10K
10000 VA / 8000 W
12 V / 9 Ah x 20
4 hours recover to 90%
90% capacity
capacity
2 A ± 10% (max.)
2 A ± 10% (max.)
UPS unit:
668X438X133
Battery pack: 580X438
UPS unit: 20
83
Battery pack: 63
668 X 438 X 133
27
Less than 58dB @ 1 Meter
10KR
X133
20