Figure 16 Terminal Block Connections; Table 2; Electrical Specifications - Emerson Liebert GXT3 208V 5000-10000V User Manual

Table of Contents

Advertisement

Terminal Block Connections
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not
share the same conduit. Emerson recommends using strain relief when installing the wire.

Table 2

Electrical specifications

UPS Model
GXT3-5000RT208
GXT3-6000RT208
GXT3-6000RTL630
GXT3-8000RT208
GXT3-10000RT208

Figure 16 Terminal block connections

Liebert GXT3-5000 and 6000RT208
Liebert GXT3-8000 and 10,000RT208
NOTE
1. Emerson recommends installing a UL489-approved breaker upstream of unit.
2. The installer must provide circuit breaker protection according to local codes. The utility
disconnect should be within sight of the UPS or have appropriate an appropriate lock-out.
Maintain service space around the UPS or use flexible conduit.
3. The installer must provide output distribution panels, circuit breaker protection or
emergency disconnects according to local codes. Output circuits must not share a common
conduit with any other wiring.
Recommended
(Maximum) External
Overcurrent Protection
30A
60A
L2
N
L1
OUTPUT
L2
N
L1
OUTPUT
Recommended Wire
(Including ground wire)
(75°C copper wire)
2
10AWG (4mm
)
2
6AWG (10mm
)
L2
N
L1
INPUT
L2
N
INPUT
20
Installation and Configuration
Maximum Wire
Terminal
Accepted by
Tightening
Terminal Block
Torque
2
8AWG (6mm
)
20 in-lb
(2.26 Nm)
2
4AWG (16mm
)
L1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6000rtl630Liebert gxt3 6000rtl630

Table of Contents