Planning for Microinverter Installation

The M215 is compatible with most 60-cell PV modules (to 270W or higher) and installs quickly and easily.
It works with either three-phase 208 VAC or single-phase 240 VAC services. The M215 ships with
integrated DC and AC cables and connectors. The DC connectors attach to the PV module, while the AC
connector attaches directly to the Engage Cable. No additional cabling is needed.
The Engage Cable is available in two connector spacing options and two voltage types to meet varying
site requirements. For Engage Cable ordering information, see "Engage Cable Planning and Ordering
Information" on page 29.
WARNING: Be aware that installation of this equipment includes risk of electric shock.
Normally grounded conductors may be ungrounded and energized when a ground fault is
indicated.

Compatibility and Capacity

The Enphase M215 Microinverters are electrically compatible with most 60-cell PV modules. For more
information, see "Technical Data" on page 26 of this manual. Refer to the Enphase website
(http://www.enphase.com/support) for a list of electrically compatible PV modules and approved PV
racking systems. To ensure mechanical compatibility, be sure to order the correct connector type for
both microinverter and PV module from your distributor.
WARNING: The M215 may be paired only with a 60-cell PV module.

Electrical Compatibility

Model Number
M215-60-2LL-S22
M215-60-2LL-S22-NA
M215-60-2LL-S23
M215-60-2LL-S23-NA
M215-60-2LL-S24
M215-60-2LL-S24-NA

Branch Circuit Capacity

Plan your AC branch circuits to meet the following limits for maximum number of M215s per branch when
protected with a 20-amp over-current protection device (OCPD).
Maximum number of M215s when protected with a 20 A OCPD
Service type
Split phase 240 VAC
Three phase 208 VAC
Utility service requirements: The M215-60-2LL works with split phase 240 VAC service
or with three phase 208 VAC service.
7
Works with PV Module Type
60-cell PV module
WARNING: The M215 can be
paired only with a 60-cell PV
module.
Max M215s per AC branch circuit
 2013 Enphase Energy Inc.
M215 Installation and Operation
PV Module Connector Type
MC-4 Type 2 Locking or
Amphenol H4 Locking
Tyco Solarlock Locking
SMK
17
25
141-00012 Rev 05