Carrier Infinity ICS 58MVC 100 Series Installation Instructions Manual page 44

Direct vent 4-way multipoise condensing gas furnace
Hide thumbs Also See for Infinity ICS 58MVC 100 Series:
Table of Contents

Advertisement

g
1. Fold heat tape in half and wrap on itself 3 times.
2. Locate heat tape between sides of condensate trap back.
(See Fig. 46.)
3. Use wire ties to secure heat tape in place. Wire ties can be
positioned in notches of condensate trap sides. (See Fig.
46.)
4. Wrap field drain pipe with remaining heat tape, approxim-
ately 1 wrap per ft. (.3M).
5. When using field-supplied
heat tape, follow heat tape
manufacturer's
instructions
for
all other
installation
guidelines.
START-UP,
ADJUSTMENT
AND
SAFETY
CHECK
Step 1 -- General
1. Furnace must have a 115-v power supply properly con-
nected and grounded.
NOTE:
Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control status indicator light flashes rapidly
and furnace does not operate.
2. Thermostat wire connections
at terminals R, W/W1, G,
and Y/Y2 must be made at 24-v terminal block on furnace
control.
3. Natural gas service pressure must not exceed 0.5 psig (14-
in. wc), but must be no less than 0.16 psig (4.5-in. wc).
4. Blower access panel must be in place to complete 115-v
electrical circuit to furnace.
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit
operation or ped\,rmance satisfaction.
These furnaces are equipped with a manual
reset limit
switch in burner box. This switch opens and shuts off
power to the gas valve if an overheat condition
(flame
rollout) occurs in burner enclosure.
Correct inadequate
combustion-air
supply
or improper
venting
condition
before resetting switch. DO NOT jumper this switch.
Before operating furnace, check flame rollout manual reset switch
for continuity. If necessary, press button to reset switch.
Step 2 -- Select
Setup
Switch
Positions
Air Conditioning
(A/C) Setup Switches
The air conditioning setup switches are used to match furnace
airflow to cooling unit used.
To set the desired cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate A/C setup switches on furnace control. (See Fig.
33.)
3. Determine air conditioning tonnage used.
4. Use Fig. 47 or wiring schematic to determine proper setup
position of A/C switches. (See Fig. 48 and Fig. 49.)
NOTE:
Excessive airflow caused by improper A/C switch setup
may cause condensate blow-off in cooling mode.
5. Replace main furnace door and blower access panel.
NOTE:
EAC-1 terminal is energized whenever blower operates.
HUM terminal is only energized when blower is energized in
heating.
Continuous
Fan (CF) Setup Switches
The CF setup switches are used to select desired airflow when
thermostat is in continuous fan mode or to select low-cooling
airflow for two-speed
cooling units. This setup feature allows
continuous fan airflow or low-cooling
airflow to be adjusted. To
set desired continuous fan airflow or low-cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate CF setup switches on furnace control. (See Fig.
33.)
3. Determine desired continuous fan airflow or low-cooling
airflow.
4. Use Fig. 47 or wiring schematic to determine proper setup
position of CF switches. (See Fig. 48 and Fig. 49.)
5. Replace main furnace door and blower access panel.
AIR CONDITIONING
(A/C) OR CONTINUOUS-FAN
(CF)
AIRFLOW SELECTION CHART
BASED ON 350 CFM/TON
(SETUP SWITCH SW1-5 OFF)
SETUP SWITCH SW3 POSITIONS
MODEL
m_-'-i_
mll:_o,
mll:_co
mll:_co
ml---l_
mr,,-l_
mr-leo
mr,,-l¢_
060, 3.5T080
DEF.
5252
700
875
10501
1225
1225
1225
5T080,
100
DEF.
7002
875
1050
1225
1400
1750_
1750
120
DEF.
700
8752
1050
1225
1400
17501
2100
BASED ON 400 CFM/TON
(SETUP SWITCH SWl-5
ON)
SETUP SWITCH SW3 POSITIONS
MODEL
q,---,,_
%--,,,.,
°E::a_.
o,_..,,_
mi._i_
ml,--i_
_l--ic,_
ml'--i¢..,o
ml[_lc,:
mr--i_,
_l'--io_
mr--ioj
060, 3.5T080
DEF.
6002
800
1000
1200_
1400
1400
1400
5T080,
100
DEF.
8002
1000
1200
1400
1600
2000_
2000
120
DEF.
800
10002
1200
1400
1600
2000_
2100
DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM
A07424
Fig. 47 - A/C or CF Airflow Selection Chart Based on 350
and 400 CFM/Ton
Setup
Switches
(SW1)
The furnace
control
has 8 setup switches
that may be set to meet
the application
requirements.
To set these setup switches
for the
@propriate
requirement:
1. Remove
main furnace
door and blower
access panel.
2. Locate setup switches
on furnace control.
(See Fig. 33.)
3. See Table 9 for setup switch
description.
(See Fig. 48 and
Fig. 49.)
4. Replace
main furnace
door and blower
access panel.
NOTE:
If a bypass
humidifier
is used,
setup
switch
SW1-3
(Low
Heat
Rise
Adjust)
should
be
in
ON
position.
This
compensates
for the increased
temperature
in return air resulting
from bypass.
NOTE:
If
modulating
dampers
are
used,
blower
motor
automatically
compensates
for modulating
dampers.
Additional
Setup
Switches
(SW4)
The furnace
control has 3 additional
setup switches
labeled
SW4.
(See
Fig.
33.)
Setup
switch
SW4-2
can be used
to lock
the
furnace
into medium
heat. When
setup switch
SW4-2
is ON the
furnace
will remain
at medium
heat until W/W1
is de-energized
to end a heating
cycle or when both W/W1
and W2 are energized.
When both W/W1
and W2 are energized
the furnace
will run at
high heat. The other 2 setup switches
are currently
not used for
anything.
When setup switch
SW4-2
is ON it will over ride setup
switch SW1-2
if it is ON. To activate
setup switch SW4-2:
1. Remove
main furnace
door and blower
access panel.
44