The refrigerant (tube) side maximum working pressure is 300 psig (2068 kPa). The water side
working pressure is 152 psig (1048 kPa). Each evaporator is designed, constructed, inspected, and
stamped according to the requirements of the ASME Boiler and Pressure Vessel Code. Double
thickness insulation is available as an option.
Phase Voltage Monitor (Optional)
Factory settings are as follows:
  Trip Delay Time, 2 seconds
  Voltage Setting, set at nameplate voltage.
  Restart Delay Time, 60 seconds
72
AGZ 025D through 190D
OMM 1166-1