Transitions between these states are shown in the following diagram.
T1 – Off to Preopen
No compressors are running and any compressor on circuit is commanded to start (see unit capacity
control)
T2 – Preopen to Run
5 seconds has passed
T3 – Run to Pumpdown
Any of the following are required:
Last compressor on circuit is commanded to stop
Unit State = Pumpdown
Circuit switch is open
Circuit mode is disable
Circuit Pumpdown alarm is active
T4 – Pumpdown to Off
Any of the following are required:
Evaporator Pressure < Pumpdown Pressure Value
Unit State = Off
Circuit Rapid Stop alarm is active
T5 – Run to Off
Any of the following are required:
Unit State = Off
Circuit Rapid Stop alarm is active
A low ambient start attempt failed
T6 – Preopen to Off
Any of the following are required:
Unit State = Off
Unit State = Pumpdown
Circuit switch is open
Circuit mode is disable
Circuit Rapid Stop alarm is active
Circuit Pumpdown alarm is active
30
POWER
OFF
ON
PUMPDOWN
AGZ 025D through 190D
PREOPEN
T 6
T 2
RUN
T 3
OMM 1166-1