Unit Level Setpoints:
Description
Mode/Enabling
Unit Enable
Network Unit Enable
Control source
Available Modes
Network Mode Command
Staging and Capacity Control
Cool LWT 1
Cool LWT 2
Ice LWT
Network Cool Set Point
Network Ice Set Point
Startup Delta T
Shut Down Delta T
Max Pulldown
Nominal Evap Delta T
Demand Limit Enable
Network Capacity Limit
LWT Reset Enable
Configuration
Power Input
Evap Control
Number of Compressors
Expansion Valve Type
Fan VFD enable
Number of fans
Timers
Evap Recirc Timer
Stage Up Delay
Stage Down Delay
Stage Delay Clear
Start-start timer
Stop-start timer
Clear Cycle Timers
Ice Time Delay
Clear Ice Timer
Sensor Offsets
Evap LWT sensor offset
Evap EWT sensor offset
OAT sensor offset
Alarm Settings
Low Evap Pressure Unload
OMM 1166-1
Default
Enable
Disable
Local
Cool
Cool
7°C (44.6°F)
7°C (44.6°F)
4.4°C (39.9°F)
7°C (44.6°F)
4.4°C (39.9°F)
5.6°C (10.1°F)
0.3°C (0.5°F)
0.6°C/min (1.1°F/min)
5.6 °C (10.1°F)
Off
100%
Off
Single Point
#1 Only
4
Thermal
No
4
30
240 sec
30 sec
No
15 min
5 min
No
12
No
0°C (0°F)
0°C (0°F)
0°C (0°F)
689.5 KPA(100 PSI)
AGZ 025D through 190D
Range
Disable, Enable
Disable, Enable
Local, Network
Cool, Cool w/Glycol, Cool/Ice w/Glycol
Ice, Test
Cool, Ice
See
Ranges
Auto Adjusted
, page 19
See
Ranges
Auto Adjusted
, page 19
-9.5 to 4.4 °C (14.9 to 39.9 °F)
See
Auto Adjusted
Ranges
, page 19
-9.5 to 4.4 °C (14.9 to 39.9 °F)
0.6 to 8.3 °C (1.1 to 14.9 °F)
0.3 to 1.7 °C (0.5 to 3.1 °F)
0.1 to 2.7 °C/min (0.2 to 4.9 °F/min)
3.3 to 8.9 °C (5.9 to 16 °F)
Off, On
0 to 100%
Off, On
Single Point, Multi Point
#1 Only, #2 Only, Auto,
#1 Primary, #2 Primary
4,6
Thermal, Electronic
No, Yes
4,6,8,10,12,14
15 to 300 seconds
120 to 480 sec
20 to 60 sec
No, Yes
10-60 minutes
3-20 minutes
No, yes
1-23 hours
No,Yes
-5.0 to 5.0 °C (-9.0 to 9.0 °F)
-5.0 to 5.0 °C (-9.0 to 9.0 °F)
-5.0 to 5.0 °C (-9.0 to 9.0 °F)
See section 5.1.1
17