Table 12, Digital Outputs
DO1
Evaporator Water Pump 1
DO2
Alarm Indicator
DO3
Circuit 1 Fan Output 1
DO4
Circuit 1 Fan Output 2
DO5
Circuit 1 Fan Output 3
DO6
Circuit 1 Fan Output 4
DO7
Circuit 2 Fan Output 1
DO8
Circuit 2 Fan Output 2
DO9
Circuit 2 Fan Output 3
DO10
Circuit 2 Fan Output 4
Compressor Module 1
Analog Inputs
X1
Circuit 1 Suction Temperature
X2
Circuit 1 Evaporator Pressure
X4
Circuit 1 Condenser Pressure
Digital Inputs
X6
Circuit 1 Switch
X7
Circuit 1 MHP Switch
X8
Circuit 1 Motor Protection
DI1
Circuit 1 (or Unit) PVM/GFP
Digital Outputs
DO1
Compressor #1
DO2
Compressor #3
DO3
Compressor #5
DO4
Evaporator Water Pump 2
DO5
Circuit 1 Hot Gas Bypass SV
DO6
Circuit 1 Liquid Line SV
Compressor Module 2
Analog Inputs
Description
X1
Circuit 2 Suction Temperature
X2
Circuit 2 Evaporator Pressure
X4
Circuit 2 Condenser Pressure
Digital Inputs
X6
Circuit 2 Switch
X7
Circuit 2 MHP Switch
X8
Circuit 2 Motor Protection
DI1
Circuit 2 PVM/GFP
Note: The Motor Protection and MHP input signal are wired in series. If Motor Protection input is
open, MHP Switch input will also be open.
OMM 1166-1
Description
Description
Description
Description
Description
Output Off
Pump Off
Alarm Not Active
Fan(s) Off
Fan(s) Off
Fan(s) Off
Fan(s) Off
Fan(s) Off
Fan(s) Off
Fan(s) Off
Fan(s) Off
Signal Type
NTC 10k
Voltage
Voltage
Signal Off
Circuit Disable
Circuit Enable
Fault
No fault
Fault
No fault
Fault
No fault
Output Off
Compressor Off
Compressor Off
Compressor Off
Pump Off
Solenoid Closed
Solenoid Closed
Signal Type
NTC 10k
Voltage
Voltage
Signal Off
Circuit Disable
Fault
Fault
Fault
AGZ 025D through 190D
Output On
Pump On
Alarm Active
Fan(s) On
Fan(s) On
Fan(s) On
Fan(s) On
Fan(s) On
Fan(s) On
Fan(s) On
Fan(s) On
Expected Range
340 to 300k Ω
0.4 to 4.6 volts
0.4 to 4.6 volts
Signal On
Output On
Compressor On
Compressor On
Compressor On
Pump On
Solenoid Open
Solenoid Open
Expected Range
340 to 300k Ω
0.4 to 4.6 volts
0.4 to 4.6 volts
Signal On
Circuit Enable
No fault
No fault
No fault
15