Supervisory Operation; Disable/Enable Operation; Waterflow Circuits Operation - Fire-Lite Alarms MRP-2001E Installation, Operation, And Programming Manual

Deluge preaction control
Table of Contents

Advertisement

Supervisory Operation

Fourth line in display:
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 03 for March, 08 for the 8th day
of the month and 06 for the year 2006
4.6 Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
The piezo sounder pulses ½ second On and ½ second Off
The Supervisory indicator flashes ½ second On and ½ second Off
The LCD displays the status label Active Supervisory along with the device name, type,
adjective/noun, associated zones and time/date
The output circuits programmed as Supervisory NAC are activated
The supervisory relay is activated
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
A typical Supervisory event would be displayed as illustrated in the following:
In the preceding example:
Note that, like alarms, supervisory signals latch (except when programmed for supervisory
autoresettable). Supervisory alarms do not cause resound as do other alarm conditions. Open
circuits in supervisory wiring are processed by the control panel the same way as other trouble
conditions. Refer to "Alarm Operation" on page 88, for a description of the information displayed
on the control panel LCD.

4.7 Disable/Enable Operation

Input zones which are disabled do not cause an alarm or any zone activation. Disabled NACs are
held in the off state. Disabled zones/NACs are treated as if they were in trouble, with the exception
being the LCD status label that will be displayed is DISABL.
Note that disabled Releasing Circuits are treated as supervisory events.

4.8 Waterflow Circuits Operation

If an alarm exists from a zone that is a waterflow non-silenceable type, the Alarm Silence key will
not function.
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
FREEZE
<ADJ> <NOUN>
ZONE 05
10:00A 030806
FROZEN SUPRV - indicates zone detector is below approximately 45
SUPERVISORY
FROZEN SUPRV
Operating Instructions
o
F
89