Installation

2.7.6.2.1 Connecting PRN-6 Printer

Remote printers require a primary AC power source. If required for the fire alarm system
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used.
The building emergency power supply may be used, as long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25
cable. One end of the cable will plug into the DB-25 connector on the PRN printer and the
other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-
9 port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a
Centronics parallel printer cable. Connect either a serial or parallel printer, but not both at the
same time.

2.7.6.2.2 Setting Printer Options

Refer to the documentation supplied with the PRN printer for instructions on using the printer
menu controls. Set the printer options (under the menu area) as shown in the following table:
38
Table 2.2 PRN-6 Setup Options
Option
Setting
Font
HS Draft
LPI
ESC Character
Bidirectional Copy
CG-TAB
Graphic
Country
E-US ASCII
Auto CR
Color Option
Not Installed
Formien
Lines
6LPI=60
Standard
Exec 10.5
Option
CPI
6 LPI
Skip
ESC
Emulate
ON
I/O
Buffer
Serial
OFF
Baud
Format
Protocol
Character Set
SI.Zero
Auto LF
PAPER
BIN 1
BIN 2
SINGLE
PUSH TRA
PULL TRA
PAP ROLL
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
ANN-BUS Devices
Setting
10CPI
0.5
Epson FX-850
40K
9600 or 2400
7 Bit, Even, 1 Stop
XON/XOFF
Standard
On
On
12/72"
12/72"
12/72"
12/72"
12/72"
12/72"