Master Programming Level
TIMER
1=AC LOSS DLAY 2 HR
Timer Screen #2
SYSTEM SETUP
1=ABORT TYPE
2=TIMERS

3=BANNER

System Setup Screen #1
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007

3.5.6.1.3 AC Loss Delay

The reporting of a loss of AC power can be delayed by programming the length of the desired
delay. Press 1 while viewing Timer Screen #2 to display the following:
AC LOSS DELAY
RANGE 00-24 HOURS
A flashing cursor will appear in the lower left corner of the display. The factory default setting
is 02 hours. Type the two digit AC loss reporting delay in hours (00 to 24 hour delay). When
the second digit is entered, the display will return to AC Loss Delay Screen #1.
Note: Upon the loss of AC power at the control panel, relays programmed for AC Loss will
transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC
Loss exist in the panel, the System Trouble relay will delay activation for the duration of the AC
Loss Delay setting.
3.5.6.2 Banner
The top line of the display, which appears when the control panel is in normal mode, can be
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will
cause the following to be displayed:
1=FACTORY BANNER
2=USER BANNER
Pressing 1 while viewing the Select Banner Screen will display the following screen:
PRESS ENTER IF OK
This screen allows the user to select the factory default Banner which will be displayed when
the system is in Normal Mode of operation. Press the Enter key to accept this as the default
display. Press the Escape key to cancel and return to the Select Banner Screen.
AC Loss Delay Screen #1
SELECT BANNER
Select Banner Screen
FACTORY BANNER
User Defined Banner Screen #1
Programming
67