B.4: Template 10: Dual Hazard - Split Release - Fire-Lite Alarms MRP-2001E Installation, Operation, And Programming Manual

Deluge preaction control
Table of Contents

Advertisement

FACP Configuration Templates
B.4 Template 10: Dual Hazard - Split Release
OUTPUT CIRCUITS
#1 ALARM NAC
#2 SUPV BELL NAC
#3 RELEASE SOLENOID 1
#4 RELEASE SOLENOID 2
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Input Zone Types:
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay Timer 10 set to secs.)
Zone 4 = Supervisory
Zone 5 = Manual Release
Zone 6 = Pull Station
Output Circuit Types:
Output 1 = Alarm NAC
Output 2 = Supervisory Bell NAC
Output 3 = Release Solenoid 1 (unsupervised for shorts)
Output 4 = Release Solenoid 2 (unsupervised for shorts)
Timers
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
Activation of Input Zone 1 (2-Wire Smoke) will operate Release Solenoid 1 Output #3 and
Alarm NAC Output #1. Activation of Input Zone 2 (Fire) will operate Release Solenoid 2
Output #4 and Alarm NAC Output #1. Activation of Input 5 (Manual Release) or Input 6
(Manual Pull Station) will operate Solenoid 1 Output #3 and Solenoid 2 (Output #4) and
Alarm NAC Output #1. Release Solenoid 1 will turn off water release following time-out of
the 10 minute Soak Timer 1 and Release Solenoid 2 will turn off water release following
time-out of the 10 minute Soak Timer 2
Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1. There is a
10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
Activation of Input Zone 4 (Supervisory) will operate the Supervisory Bell NAC Output #2
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 5 (Manual Release) or Zone 6 (Pull
Station) will operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 4 (Supervisory) will operate the Supervisory Relay
112
TEMPLATE 10: DUAL HAZARD - SPLIT RELEASE
1
2
2-WIRE SMOKE
FIRE
X
X
X
X
Template 10: Dual Hazard - Split Release
INPUT ZONES
3
4
WATERFLOW
SUPV.
X
X
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
5
6
MANUAL
PULL
RELEASE
STATION
X
X
X
X
X
X