Control Logic - Flow Chart - Raypak 259 Installation & Operating Instructions Manual

84 professional gas-fired pool & spa heater
Table of Contents

Advertisement

CONTROL LOGIC - FLOW CHART

Power On
Is the water
temperature displayed?
YES
Push MODE
button to select
"Pool" or "Spa"
Push UP or DOWN
button to scroll to
desired temperature
Water temperature
and set
temperature
displayed?
YES
"Purge"
"Spark"
Water temp displayed?
(rectified)
YES
Heater Fired?
YES
END
• Check On/Off switch (under lid on control panel)
NO
• Check for 120/240 volts to the transformer
(time clock, circuit breaker, wire connections)
• Check for 24 volts to Circuit Board (P6 connector)
remote function off. See page 38 for instructions.
NO
"Sensor Failure," "Sensor Open" or "Sensor Short" -
Temperature sensor out of range (replace sensor)
Inspect thermister, wires, and connector at Terminal P1
Check resistance value of the thermister. Reference to chart below.
Replace thermister if not within 10% of values shown below.
If okay, replace Circuit Board.
Temp Degrees F 40
Resistance (k)
If okay, replace Circuit Board
"Water Sw Open"
"Hi Limit 1 Fault"
"Hi Limit 2 Fault"
"Clock/Fireman Sw"
NO
"Blocked Vent"
"EOL" (at start-up)
"Ignition Lockout"
"Ignition Failure"
Verify power at MV on P-4 Terminal on digital circuit board.
NO
Verify power to valve MV voltage. (Replace valve.)
"Remote" and Water Temperature displayed
(a remote control is controlling the heater)
Note: Disconnect the remote by turning the
NO
Is a fault code displayed and flashing?
YES
Diagnostic Readouts
Sensor Failure
Sensor resistance at various temperatures
50
60
70
261.1 199.0 153.1 118.8 93.0 73.3
Water flow switch. Verify water flow and pressure. If water
connections were reversed, verify the location and direction
of the water flow across the flow switch.
CLEAN FILTER / STRAINER - backwash if neccessary.
High limit switch. Verify water flow. Inspect internal
bypass valve.
Fireman or Remote switch connected to safety loop is in the
OFF mode.
Vent switch open. Check connections to the board.
Check for blockages in the vent.
Check for stuck MODE button.
Ignition lockout. Check spark (bad ignition circuit or
hi-tension wire).
Ignition failure. Verify gas to the heater. Verify valve operation
(gas present at tube fitting).
43
80
90
100
106
58.3
51.0