ENTERING THE ADVANCED INSTALLER SETTINGS MENU

ENTERING THE ADVANCED INSTALLER SETTINGS MENU
The T-32-P contains factory defaults for all Advanced
Installer Settings. Depending upon the user and
equipment application, some settings may need to be
changed.
To enter the Advanced Installer Settings menu, push the
O/RIDE
button once then hold it down (15 seconds) until
the number "
88:15
" is displayed on the LCD. Using the
( ) ( ) arrow button, adjust the value until it reads
"
88:32
" and then press the
menu. You can move forward or backwards through the
menu by pressing the
O/RIDE

ADVANCED INSTALLER SETTINGS MENU

Symbol Default
88
PN
32
LC
LC
00
Programmable Mode
Manual Mode
(Sw6=OFF)
HL
HL
90
CL
CL
50
CF
CF
F
CI
C1
0.0
8C
TC
12
88
TD
0
AH
AH
2.0
4 Schedules
Temporary Program Override 0 (OFF)
(Sw6=ON)
extends override to next program
(Sw8=ON)
change. 1 - 12 equals fixed hours of
override.
O/RIDE
button to enter the
or
PROG
buttons.
Function
Keyboard Lock PIN. This is the required
PIN for future entry into the Advanced
Installer Setup menu. (Range 00-99)
Keyboard Lock OFF
LC=01 - All buttons are locked except
( ) ( ) buttons.
LC=02 - All buttons are locked except
O/RIDE
and( ) ( ) buttons.
LC=03 - All buttons are locked except
MODE, O/RIDE
and ( ) ( ) buttons.
LC=04 - All buttons are locked except
MODE
and ( ) ( ) buttons.
LC=05 - All buttons are locked except
O/RIDE
button.
LC=06 - All buttons are locked.
LC=00 - Keyboard lock OFF.
LC=01 - All buttons are locked except
MODE
button.
LC=02 - All buttons are locked except
MODE
and ( ) ( ) buttons.
LC=03 -
FAN
, and
PROG
are locked.
MODE
button can only select Auto or
OFF.
LC-04 - MODE button can only select
Auto or OFF.
LC-05 - All buttons are locked.
LC-06 - Same function as LC-05.
Maximum Heating or High Temperature
Limit.(Adjustable from 41° F - 120° F)
Minimum Cooling or Low Temperature
Limit. (Adjustable from 43° F - 122° F)
Temperature Display
(Degrees F or C)
Internal Sensor Calibration
(Adjustable +/- 9° F)
Time Format
(12 or 24 Hour Clock)
Temperature Display
TD=0 - Displays set and space
temperatures.
TD=1 - Displays only the set
temperature.
After Hours Override Timer
ADVANCED INSTALLER SETTINGS MENU
Symbol Default
SC
SC
OF
SH
SH
OF
88
DB
2
F8
FO
0
FP
FP
0
88
FN
A
H3
H3
OF
88
TT
RS
AF
AF
1
8H
OH
OF
8C
OC
OF
7
Function
Leave at factory default
Leave at factory default
Leave at factory default
Advanced Fan Function
Fan runs continuously in ON mode.
FO=1 - Fan continues to run after
cooling cycle but not heating
cycle.
FO=2 - In programmable mode
(Sw6=ON), fan runs continuously with
program 1 through 4 and then in AUTO
from program 4 - 1.
FO=3 - In programmable mode
(Sw6=ON), fan control is a combination
of option 1 and 2.
Fan Purge
Adjustable from 0 - 5 minutes after
heating or cooling cycle.
Mode - Heat / Cool system.
FN=C - Cooling only system.
FN=H - Heating only system.
W2 relay only operates as auxiliary heat
in heat pump mode.
(Sw1=OFF) (Sw2=ON)
H3=EH - W2 relay controls emergency
heat.
H3=AH - Do not use this function.
H3=AL - W2 relay used for auxiliary
and emergency heat.
H3=FF - Fossil Fuel (Y is locked out
when W2 is energized.
For
NO
remote sensor
OR
1 or more
remote indoor sensor without the
onboard sensor being used.
TT=OA - For outdoor remote sensor
connection.
TT=DA - Sends measured temperature
from remote sensor via modbus but
does not display the value on the LCD.
TT=OC - For connecting dry contact
switch.
(Replaces user setpoints with
pre-programmed cooling 'OC' and
heating 'OH' setpoints)
TT=OF - For connecting dry contact
switch.
(Turns thermostat off when closed)
TT=AV - For averaging
BOTH
the
internal thermostat sensor and remote
indoor sensor(s) together.
Freeze protection ON. If thermostat is
OFF, heating will come on if room
temperature falls below 41° F.
AF=0 - No freeze protection.
Override Heating Setpoint.
(Adjustable from 41° F - 120° F)
Override Cooling Setpoint.
(Adjustable from 43° F - 122° F)