Terminal Designations; Typical System Wiring Diagram; Heat Only; Heat / 1 Cool - Jackson Systems Comfort System T-32-P Installation Manual

Universal thermostat
Hide thumbs Also See for Comfort System T-32-P:
Table of Contents

Advertisement

INSTALLING THE THERMOSTAT

TERMINAL DESIGNATIONS

Based on the T-32-P slide switch configurations,
some terminals have multiple output functions .
(Figure 3)
W2
Y2
W1
G3
G2
O/BY1 G1 R
TERMINAL DESIGNATION CHART
TERMINAL
Second Stage Heating or Auxiliary Heat
W2
Y2
Second Stage Compressor
W1
First Stage Heating
Reversing Valve
O/B
Y1
First Stage Compressor
G1
Fan Relay
R
24 Volt Hot (Jumpered to '24')
24
24 Volt Hot
24C
24 Volt Common
B
Modbus Communications
A
Modbus Communications
T
Auxiliary Input Terminal
T
Auxiliary Input Terminal
TYPICAL SYSTEM WIRING DIAGRAMS

HEAT ONLY

W2
Y2
W1
G1
R
Y1
G2
O/B
G3
HEAT 1
FAN 1
RELAY
RELAY
Switch Settings
Sw1 = OFF
Sw2 = OFF
Sw3 = OFF
Sw4 = OFF
Sw5 = Installer Preference
(ON = 4 Minutes Short Cycle Protection)
Sw6 = User Preference
(OFF = Programmable)
(ON = Non-programmable)
Sw7 = Installer Preference
(OFF = 2 Minute Run Time)
(ON = 6 Minute Run Time)
Sw8 = ON
Set FN=H in Advanced Installer Settings
(Heat Only)
FACTORY
JUMPER
Aux
Power
Coms
24 24C B A T T
FIGURE 3
DESIGNATION
24
24C
B
A
T
T
TT
MODBUS
TERMINALS
24 V
LINE
(Fan Relay)
(Heat / Cool)
(Single Stage)
(Equipment Controls Fan)
(2 Setpoints)

1 HEAT / 1 COOL

Y2
W1
W2
Y1
G2
G3
O/B
HEAT 1
RELAY
COMP 1
RELAY
Switch Settings
Sw1 = OFF
Sw2 = OFF
Sw3 = OFF
Sw4 = OFF
Sw5 = Installer Preference
(OFF = No Short Cycle Protection)
(ON = 4 Minute Short Cycle Protection)
Sw6 = User Preference
(OFF = Non-programmable)
(ON = Programmable)
Sw7 = Installer Preference
(OFF = 2 Minute Minimum Run Time)
(ON = 6 Minute Minimum Run Time)
Sw8 = ON
(Separate Heating and Cooling Setpoints)

2 HEAT / 2 COOL

W2
Y2
W1
Y1
G3
G2
O/B
HEAT 2
HEAT 1
RELAY
RELAY
COMP 2
COMP 1
RELAY
RELAY
Switch Settings
Sw1 = OFF
Sw2 = OFF
Sw3 = ON
Sw4 = OFF
Sw5 = Installer Preference
(OFF = No Short Cycle Protection)
(ON = 4 Minute Short Cycle Protection)
Sw6 = User Preference
(OFF = Non-programmable)
(ON = Programmable)
Sw7 = Installer Preference
(OFF = 2 Minute Minimum Run Time)
(ON = 6 Minute Minimum Run Time)
Sw8 = ON
(Separate Heating and Cooling Setpoints)
4
G1
R
24
24C
B
A
FAN 1
MODBUS
RELAY
24 V
(Fan Relay)
(Heat / Cool)
(Single Stage)
(Equipment Controls Fan)
24
24C
B
A
G1
R
FAN 1
MODBUS
RELAY
24 V
(Fan Relay)
(Heat / Cool)
(Two Stage)
(Equipment Controls Fan)
T
T
TT
TERMINALS
LINE
T
T
TT
TERMINALS
LINE