Remote Sensor Installation Instructions; Specifications - Jackson Systems Comfort System T-32-P Installation Manual

Universal thermostat
Hide thumbs Also See for Comfort System T-32-P:
Table of Contents

Advertisement

BASIC TROUBLE SHOOTING
SYMPTOM
POSSIBLE FAULT AND REMEDY
Wrench icon flashes
This is not a fault. Commissioning mode is
on LCD
enabled and time delays are overridden.
Change CD=1 to CD=0 in the Advanced
Outdoor temperature
Check wiring to outdoor sensor. Make sure
does not display.
that TT=OA in the Advanced Installer menu.
Dashes (---) appear
on the LCD.
This is not a fault. The T-32-P has a built-in
Heating or Cooling is
minimum equipment run time of either 2 or 6
flashing while the
minutes. Sw6 may set for 6 minutes (ON)
HVAC system is
which is keeping the equipment on after the
running.
thermostat reaches setpoint. Try setting
Lock icon flashes
This is not a fault. HL and CL restrict the
when trying to set a
heating and cooling setpoints. The limit
higher heating or
values can be changed in the Advanced
lower cooling
Installer menu.
temperature.
The T-32-P can display in either Fahrenheit
Thermostat
or Celsius. Change CF=C or F in the
displays wrong
Advanced Installer menu.
temperature.
The thermostat is set to Fan ON. Set the
The fan continues
thermostat to Auto Fan. The fan purge
to run after a
mode is set to run the fan for a fixed period
heating or cooling
of time after the equipment shuts off.
call is satisfied.
Change the FP value in the Advanced
Installer menu.
Some buttons on
Lock values have been set. Refer to LC
the thermostat do
settings in the Advance Installer menu.
not function.
Make sure that the plastic tab on the
Thermostat clock
does not keep
internal fitted battery is removed so that the
proper time.
battery is operational.

REMOTE SENSOR INSTALLATION INSTRUCTIONS

The T-32-P can use an indoor remote sensor or
multiple sensors for temperature averaging or as
an outdoor sensor for temperature display or a
control function depending upon the thermostat
configuration.
INDOOR SENSOR INSTALLATION
Locate the sensor in the same manner as a
thermostat. Mount the sensor 18" away from any
outside wall. Do not install the sensor behind
doors, in corners or other dead air spaces. Keep
the sensor away from direct air flow, supply
registers or near sources
and appliances. The maximum wire length from the
sensor to the thermostat is 300 feet. Use a
separate 18-2 thermostat cable for sensor wiring.
Prior to wiring the sensor to the thermostat, use an
ohm-meter or multimeter to measure the
resistance of the sensor. Measure at the end of the
wires that will connect to the thermostat.
of heat such as lamps
Confirm the resistance value (within 5%) to the
temperature where the sensor is mounted.
Disconnect power to the thermostat when wiring
the sensor to the 'T' and 'T' terminals. Strip only as
much insulation off of the wires as necessary to
provide a good contact with the terminals. The
sensor is not polarity specific so either sensor lead
may be connected to either terminal on the
OUTDOOR SENSOR INSTALLATION
Mount the sensor on a vertical exterior surface
below an overhang. Choose a location protected
from direct sunlight and exposure to excessive
moisture. Follow the same wiring and test
procedures as installing an indoor sensor.
SENSOR CALIBRATION CHART
Temperature
Resistance
(°F)
(k )
30
34.6
40
26.1
50
19.9
60
15.3

SPECIFICATIONS

Input Voltage
Relay Rating
Operating Temperature
Operating RH
Storage Temperature
Size
LCD Display Size
Temperature Sensor
Voltage
Resistance
Tolerance
Stage Delays
Timed Upstage Delay
Short-cycle Delay
Display Resolution
Control Range
Outdoor Air Temperature Range
Back Light
Optimized Start/Stop Method
Communications Protocol
Approvals
Warranty
The T-32-P can be configured for 3-speed fan and
single setpoint control.
For information regarding these features, contact
Jackson Systems at 1-888-652-9663
11
Temperature
Ω
(°F)
70
80
90
100
24 VAC 50/60 Hz
24 VAC @ 1Amp maximum
per relay
32° F to 122° F
0-95% (non-condensing)
32° F to 105° F
4-7/16" W x 4-1/16" H x 7/8" D
2-3/4" W x 1-7/8" H
10K NTC type 3
20-30 VAC
10k @ 77 F
Ω
°
+/- 3% @ 77 F
°
Minimum temperature change
over time
5 - 90 minutes
Off to 4 minutes
0.1° F
Off to 105° F
-10° F to 140° F
Blue EL (Electro Luminescent)
Time to start vs. temperature
differential
Modbus
FCC (Part 15) (Pending)
C-tick
5 years
Resistance
(k )
Ω
11.9
9.4
7.4
5.9