Heat / 2 Cool Dual Fuel; Entering The Advanced Installer Settings Menu - Jackson Systems Comfort System T-32-P Installation Manual

Universal thermostat
Hide thumbs Also See for Comfort System T-32-P:
Table of Contents

Advertisement

TYPICAL SYSTEM WIRING DIAGRAMS

3 HEAT / 2 COOL DUAL FUEL

Switch Settings
Sw1 = ON
Sw2 = ON
Sw3 = ON
Sw4 = Reversing Valve
Sw5 = ON
Sw6 = User Preference
Sw7 = User Preference
Sw8 = OFF
IMPORTANT:
If an outdoor sensor is used and High or Low Balance Point control is required, set HB and LB in the
Advanced Installer menu.

ENTERING THE ADVANCED INSTALLER SETTINGS MENU

The T-32-P contains factory defaults for all Advanced Installer Settings. Depending upon the user
and equipment application, some settings may need to be changed.
To enter the Advanced Installer Settings menu, push the
seconds) until the LCD displays
through the menu by pressing the
ADVANCED INSTALLER SETTINGS MENU
Symbol
Default
LC
00
Programmable Mode
(Sw6=ON)
LC
00
Non-programmable
Mode
(Sw6=OFF)
9
W1
Y2
W2
G
Y1
O/B
FOSSIL
REV
FAN 1
FUEL
VALVE
RELAY
COMP 2
COMP 1
RELAY
RELAY
(Heat Pump)
(Multi-stage)
(Dual Fuel)
(OFF = 'O')
(ON = 'B')
(Thermostat Controls Fan)
(OFF = Non-Programmable)
(ON = Programmable)
(OFF = 4 Schedules per Day)
(ON = 2 Schedules per Day)
(4 Minute Short Cycle Protection)
LC
which is the first menu item. You can move forward or backwards
O/RIDE
or
Function
Keypad Lockout
LC=00 - All buttons are unlocked
LC=01 - All buttons are locked except ( ) ( ) buttons
LC=02 - All buttons are locked
LC=00 - All buttons are unlocked
LC=02 - All buttons locked except ( ) ( ) buttons
LC=03 - PROG button is locked
LC=04 - All buttons are locked
24
24C
B
R
MODBUS
24 V
O/RIDE
button once, then hold it down (15
PROG
buttons.
A
T
T
TT
TERMINALS
LINE