TYPICAL SYSTEM WIRING DIAGRAMS

2 HEAT / 1 COOL HEAT PUMP

Y2
W1
W2
Y1
G1
G3
G2
O/B
AUX
REV
FAN 1
HEAT
VALVE
RELAY
COMP 1
RELAY
Switch Settings
Sw1 = OFF
Sw2 = ON
Sw3 = OFF
Sw4 = Reversing Valve
(OFF = 'O' - RV Energized in Cooling)
(ON = 'B' - RV Energized in Heating)
Sw5 = Installer Preference
(OFF = No Short Cycle Protection)
(ON = 4 Minute Short Cycle Protection)
Sw6 = User Preference
(OFF = Non-programmable)
(ON = Programmable)
Sw7 = Installer Preference
(OFF = 2 Minute Minimum Run Time)
(ON = 6 Minute Minimum Run Time)
Sw8 = ON
(Separate Heating and Cooling Setpoints)

3 HEAT / 2 COOL HEAT PUMP

W2
Y2
W1
G1
Y1
G2
O/B
G3
AUX
REV
FAN 1
HEAT
VALVE
RELAY
COMP 2
COMP 1
RELAY
RELAY
Switch Settings
Sw1 = OFF
Sw2 = ON
Sw3 = ON
Sw4 = (Reversing Valve)
(OFF = 'O' - RV Energized in Cooling)
(ON = 'B' - RV Energized in Heating)
Sw5 = Installer Preference
(OFF = No Short Cycle Protection)
(ON = 4 Minute Short Cycle Protection)
Sw6 = User Preference
(OFF = Non-programmable)
(ON = Programmable)
Sw7 = Installer Preference
(Off = 2 Minute Minimum Run Time)
(ON = 6 Minute Minimum Run Time)
Sw8 = ON
(Separate Heating and Cooling Setpoints)
24
24C
B
A
T
R
TT
MODBUS
TERMINALS
24 V
LINE
(Fan Relay)
(Heat Pump)
(Single Stage)
24
24C
B
A
T
R
TT
MODBUS
TERMINALS
LINE
24 V
(Fan Relay)
(Heat Pump)
(Two Stage)

2 HEAT / 1 COOL DUAL FUEL

Y2
W2
G3
G2
FOSSIL
T
FUEL
Switch Settings
Sw1 = OFF
Sw2 = ON
Sw3 = OFF
Sw4 = Reversing Valve
Sw5 = Installer Preference
Sw6 = User Preference
Sw7 = Installer Preference
Sw8 = ON

3 HEAT / 2 COOL DUAL FUEL

Y2
W2
G3
G2
FOSSIL
FUEL
T
COMP 2
RELAY
Switch Settings
Sw1 = OFF
Sw2 = ON
Sw3 = ON
Sw4 = Reversing Valve
Sw5 = Installer Preference
Sw6 = User Preference
Sw7 = Installer Preference
Sw8 = ON
5
W1
24
24C
Y1
G1
R
O/B
REV
FAN 1
VALVE
RELAY
COMP 1
RELAY
(OFF = 'O' - RV Energized in Cooling)
(ON = 'B' - RV Energized in Heating)
(OFF = No Short Cycle Protection)
(ON = 4 Minute Short Cycle Protection)
(OFF = Non-programmable)
(ON = Programmable)
(OFF = 2 Minute Minimum Run Time)
(ON = 6 Minute Minimum Run Time)
(Separate Heating and Cooling Setpoints)
W1
24
24C
Y1
G1
R
O/B
REV
FAN 1
VALVE
RELAY
COMP 1
RELAY
(OFF = 'O' - RV Energized in Cooling)
(ON = 'B' - RV Energized in Heating)
(OFF = No Short Cycle Protection)
(ON = 4 Minute Short Cycle Protection)
(OFF = Non-programmable)
(ON = Programmable)
(OFF = 2 Minute Minimum Run Time)
(ON = 6 Minute Minimum Run Time)
(Separate Heating and Cooling Setpoints)
B
A
T
T
TT
MODBUS
TERMINALS
LINE
24 V
(Fan Relay)
(Heat Pump)
(Single Stage)
B
A
T
T
TT
MODBUS
TERMINALS
24 V
LINE
(Fan Relay)
(Heat Pump)
(Two Stage)

Hide quick links: