Automatic Backup; Resetting Factory Defaults; Calibrating The Temperature Sensor Offset - Jackson Systems Wireless Comfort WCT-32 Installation Manual

7-day programmable, battery powered thermostat
Hide thumbs Also See for Wireless Comfort WCT-32:
Table of Contents

Advertisement

Option
CANCEL
22

Automatic Backup

The HVAC Control Module saves the previous 24-
hour pattern of heating, cooling and fan calls in
memory. Should the module lose
communications with the thermostat because of a
low battery or other reason, the module
automatically repeats the call pattern of the
previous 24 hours.
Press the
key to select
NEXT
or
key to set the
Up
Down
(00). It is highly recommended that this option be
left on.
Option
CANCEL
23
Calibrating the Temperature
Sensor Offset
Typically, it is not necessary to adjust the
temperature calibration offset from the factory
setting. If calibration is necessary, a high quality
electronic digital thermometer must be used. Place
the thermometer sensor probe next to the
thermostat sensor and allow five minutes before
Set To
NEXT
ENTER
and the
Option 16
Backup
(01) or
On
Off
Set To
NEXT
ENTER
comparing the temperature readings. Press and
hold the
key until the calibration screen
MENU
appears as shown. Use the
to adjust the temperature calibration offset.
Press the
key to save the setting and
ENTER
return to normal thermostat operation.
CANCEL
MENU

Resetting Factory Defaults

To reset the factory defaults, remove the batteries
and re-install them while holding down the
SYSTEM
key. All prior changes will default to the
factory settings. This will require resetting the
time of day and programming schedules if
necessary. Refer to the Installer Options Chart
default settings to make any additional changes.
This installation manual should not be left
with unauthorized users as it contains
installer setup functions which, if not
correctly set, may cause damage to the HVAC
equipment or seriously affect performance.
This manual is to be used in conjunction with the
supplied User Manual.
Although great care has been taken in
preparation of this manual, Jackson Systems
takes no responsibility for errors or
omissions contained herein. It is the
responsibility of the installer to ensure that
this thermostat and the equipment connected
to it operate in a safe and efficient manner.
Due to ongoing product improvements, Jackson
Systems reserves the right to change the
specifications of the WCT-32 thermostat or its
components without notice.
All rights reserved.
©
Jackson Systems, LLC 2010
Intellectual rights apply.
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
8
Up
and
Down
keys
Inside
NEXT
ENTER
06-1055-030211