Miscellaneous System Fields; Test Restore Report Code - ADEMCO VISTA-20PS Series Installation And Setup Manual

Hide thumbs Also See for VISTA-20PS Series:
Table of Contents

Advertisement

Installation and Setup Guide
FIELD
TITLE and DATA ENTRIES
Bypass Restore Report Code
*72
0 = no report
1-F = see description above *59
AC Restore Report Code
*73
0 = no report
1-F = see description above *59
Low Bat Restore Report Code
*74
0 = no report
1-F = see description above *59
RF Xmtr Low Batt. Restore Code
*75
0 = no report
1-F = see description above *59

Test Restore Report Code

*76
0 = no report
1-F = see description above *59

Miscellaneous System Fields

FIELD
TITLE and DATA ENTRIES
Daylight Saving Time
*77
Start/End Month
0 = Disabled
1 = Jan
2 = Feb
3 = Mar
Daylight Saving Time
*78
Start/End Weekend
0 = disabled
1 = first
2 = second
3 = third
Output Device Mapping Menu Mode
*79
Output Programming Menu Mode
*80
Zone List Programming Menu Mode
*81
Alpha Descriptor Programming
*82
Menu Mode
Auto-Stay Arm
*84
0 = no
1 = partition 1 only
2 = partition 2 only
3 = both partitions
Cross Zone Timer (in seconds)
*85
0 = 15 secs
1 = 30 secs
2 = 45 secs
3 = 60 secs
4 = 90 secs
5 = 2 min
4-6
4 = April
# + 10 = Oct
# + 11 = Nov
# + 12 = Dec
4 = fourth
5 = last
6 = next to last
7 = third to last
6 = 2-1/2 min #+12 = 8 min
7 = 3 min
#+13 = 10 min
8 = 4 min
#+14 = 12 min
9 = 5 min
#+15 = 15 min
#+10 = 6 min
#+11 = 7 min
EXPLANATION
This is sent when a zone that has been bypassed is unbypassed.
UL: Required for UL commercial burglar alarm installations.
Sent when AC power has been restored after an AC power outage.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
Sent when a system low-battery condition is restored to normal.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
Sent when a transmitter's low battery condition is restored (i.e., new
battery installed).
UL installations: must be enabled if wireless devices are used.
Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
This is sent when the Test mode is exited.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
EXPLANATION
Enter the start and end month for daylight savings time, if
applicable to the region.
Enter the start and end weekend for daylight savings time, if
applicable to the region.
Use this menu mode to enter output devices/powerline carrier
devices into the system. See Output Device Programming
section for procedures.
Use this menu mode to define output functions for use with
output devices/powerline carrier devices. See Output
Programming section for procedures.
Use the menu mode to define zone lists. See Zone List
Programming section.
Use this menu mode to assign alpha descriptors to zones and/or
create partition descriptors (VISTA-20P).
If enabled, the system will automatically change AWAY mode to
STAY mode if the entry/exit door is not opened and closed
within the exit delay time after a user arms in AWAY mode
from a wired keypad (non-RF device). An Opening report
followed by an Armed Stay report is sent to the Central Station.
If the door is opened and closed within the exit delay period, the
system remains in AWAY mode.
Any RF device that arms the system AWAY overrides this
feature and the system remains armed in the AWAY mode.
Sets the maximum amount of time in which two cross zones
must be tripped in an armed system to send an alarm message
to the Central Station. If only one cross zone is tripped during
this time, a trouble message (CID code 380) for that zone is sent
to the Central Station.
Assign cross zone pairs in zone list 4.