Keypads; Wireless Receiver, Transmitters, And Wireless Keys (Keyfobs); Pager Programming - ADEMCO VISTA-20PS Series Installation And Setup Manual

Hide thumbs Also See for VISTA-20PS Series:
Table of Contents

Advertisement

Installation and Setup Guide

Keypads

Keypads are identified by predefined addresses (starting at address 16) as follows:
Address
Keypad
16
keypad 1
17
keypad 2
18
keypad 3
19
keypad 4
20
keypad 5
21
keypad 6
22
keypad 7
23
keypad 8
To enable keypads:
1. Set desired address at keypad (refer to keypad's instructions for setting the address).
2. Use data field program mode to enable keypad addresses, assign a partition, enable sound options
in fields *190-*196 as shown in the table above.
3. If desired, use data field *198 to turn on the display of the partition number.
4. Set the following keypad-related data fields as required by the installation:
*21 Quick Arm Enable, *23 Forced Bypass, *84 Auto STAY Arm
5. If using AUI, enable each unit in field *189 and set AUI 1 to address 1, AUI 2 to address 2.

Wireless Receiver, Transmitters, and Wireless Keys (keyfobs)

Receiver: Set the receiver's address to "00" using its DIP switches, then set the following options:
*22
RF Jam Option
*24
RF House ID Code (if using wireless keypads) for each partition
*67
Transmitter Low Battery Report Code
*75
Transmitter Low battery restore report code
Transmitters: Use *56 or *58 Zone Programming Menu modes to program zone information and
enroll transmitters (VISTA-20P: zones 9-48, buttons 49-64; VISTA-15P: zones 9-34, buttons 49-56).
Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone Programming
Menu mode to program zone information and enroll each button of the wireless keys used. Once a
wireless key is enrolled, it must be assigned to a user before it becomes active. See Adding/Deleting
Security Codes section for procedure.

Pager Programming

The system can send various reports to several pagers (VISTA-20P = up to 4; VISTA-15P = up to 2).
To program pager reporting, do the following:
1. Enter the appropriate information in the following data fields:
*160, *163, *166, *169 Pager Phone Numbers (for pagers 1-4
*161, *164, *167, *170 Pager Prefix Characters (for pagers 1-4
*162, *165, *168, *171 Pager Reporting Options by Partition
2. Enable Pager Delay, if desired, in field *172 (delays alarm reporting for ALL pagers).
3. Enable appropriate user open/close pager reports using the user attribute command
(master code + [8] + user no. + [#] [5] + [1]). Users that perform actions in partition 1 will, if
enabled, attempt to report to all pagers enabled for open/close reporting in partition 1. Users that
perform actions in partition 2 will, if enabled, attempt to report to all pagers enabled for
open/close reporting in partition 2.
4. If using latchkey pager report, define the latchkey report schedule using Scheduling mode (master
code + [#] [6] [4] then select event type "03").
5. If using a function key to manually send a message to a pager, see Function Keys on next page.
6. If reporting zone alarms and troubles to a pager, use *81 Zone List menu mode to assign the zones
associated with each pager (zone lists 9-12
† VISTA-20P supports four pagers and partitioning; VISTA-15P supports two pagers and zone lists 9
and 10 only.
3-2
Program Field
• always enabled for partition 1, all sounds enabled.
• data field *190
• data field *191
• data field *192
• data field *193
• data field *194
• data field *195
• data field *196
† These fields must be enabled for Residential
Fire, UL Residential Burglar Alarm, and UL
Commercial Burglar Alarm installations.
respectively)
respectively)
(for pagers 1-4 respectively)
).
NOTE: First keypad is address 16.