Conventional Systems; Typical Wiring Configurations - Braeburn 3020 Detailed Installer Manual

Premier series non-programmable thermostats
Hide thumbs Also See for 3020:
Table of Contents

Advertisement

Conventional Systems

Typical Wiring Configurations

NOTE: The "System Type" option will be configured in the Installer Settings section. The 3020 is a single stage
thermostat and not intended for multi stage equipment.
Heat Only or Millivolt
Set System Type to 11CONV
Rh Power Connection
W1 Heat Relay
G
Fan Relay [note 4]
C
24 Volt AC Transformer Common [note 1]
1 HEAT / 1 COOL Single or Dual Transformer
Set System Type to 11CONV
Rh 24 Volt AC Power (heating transformer) [note 2]
Rc 24 Volt AC Power (cooling transformer) [note 2]
W1 Heat Relay
Y1 Compressor Relay
G
Fan Relay
C
24 Volt AC Transformer Common [note 1, 3]
2 HEAT / 2 COOL Single or Dual transformer
Set System Type to 22CONV
Rh 24 Volt AC Power (heating transformer) [note 2]
Rc 24 Volt AC Power (cooling transformer) [note 2]
W1 Heat Relay Stage 1
W2 Heat Relay Stage 2
Y1 Compressor Relay Stage 1
Y2 Compressor Relay Stage 2 [note 4]
G
Fan Relay
C
24 Volt AC Transformer Common [note 1, 3]
Additional Wiring Options
NOTE: Additional options are configured in the
Installer Settings section.
S1
Indoor or Outdoor Remote Sensor [note 1]
S2
Hydronic Heat Only
Set System Type to 1HD
Rh 24 Volt AC Power (heating transformer)
W1 Zone Valve Power Open
V3 Zone Valve Power Close
G
Fan Relay [note 4]
C
24 Volt AC Transformer Common [note 1]
Hydronic Heat / 1 Cool
Set System Type to 11HD
Rh 24 Volt AC Power (heating transformer) [note 2]
Rc 24 Volt AC Power (cooling transformer) [note 2]
W1 Zone Valve Power Open
V3 Zone Valve Power Close
Y1 Compressor Relay
G
Fan Relay (cooling fan only)
C
24 Volt AC Transformer Common [note 1, 3]
NOTES - Conventional Systems
[1] Optional 24 Volt AC common connection.
[2] Remove factory installed jumper for dual
transformer systems.
[3] In dual transformer systems, transformer
common must come from cooling transformer.
[4] If needed for system.
Provide disconnect and overload protection as required.
NOTES - Additional Wiring Options
[1] These terminals can be used to connect a
Braeburn
indoor or outdoor remote sensor.
®
5
Installer Guide