Braeburn 3020 Detailed Installer Manual page 10

Premier series non-programmable thermostats
Hide thumbs Also See for 3020:
Table of Contents

Advertisement

No. Installer Setting
(
Notes follow this table)
11 Compressor Power Outage oF CPOP
Protection
[notes 3, 5]
12 AC Power Interrupt
Warning [note 5]
13 Compressor Short
Cycle Protection [note 6]
14 Residual Cooling
Fan Delay [note 6]
15 Indoor Remote Sensor
Control* [note 7]
16 Lockout Security Level
17 Auto Changeover
Dead Band [note 8]
18 Compressor Balance
Point [notes 3, 9]
19 Auxiliary Heat Balance
Point [notes 3, 9]
20 Heat Set Point Upper Limit 90LIM
21 Cool Set Point Lower Limit 45LIM
[note 6]
*When a Braeburn
outdoor sensor is connected, the thermostat automatically recognizes it. Press BACK and NEXT at the same
®
time to display outdoor temperature.
NOTE: Additional options such as Service Monitors, Setting the lock code, etc. are located in the User Settings –
See User manual for information on setting these options.
NOTES - Installer Settings
1 Only available if a 2 or 3 stage system type was selected in option 3.
2 Only available if a Conventional system was selected in option 3.
3 Only available if a 2 or 3 stage Heat Pump system was selected in option 3.
4 Only available if a Heat Pump system was selected in option 3.
5 Only available if the 24 Volt AC common wire is connected to the C terminal.
6 Not available if a Heat Only Hydronic system is selected in option 3.
7 Only available if a Braeburn
8 Only available if auto changeover was enabled in option 2.
9 Only available if a Braeburn outdoor sensor was connected.
Detailed Explanation of Installer Settings (also see NOTES above):
1
Temperature Scale – Selects a temperature scale of either °F or °C.
2
Auto Changeover – Selects auto changeover on or off. When auto changeover mode is enabled and
selected, the system automatically switches between heating and cooling modes. There is a 5 minute delay
when switching from heating to cooling or cooling to heating in auto changeover mode.
NOTE: Also see "Auto Changeover Dead Band" in option 17.
Installer Guide
Factory
Setting
Default
Options
oF CPOP
on CPOP
AC oF MONR
AC oF MONR Disables AC Power Interrupt Warning
AC on MONR Enables AC Power Interrupt Warning
5 CSCP
5, 4, 3, 2 or Select a compressor short cycle protection delay of 5,
0 CSCP
60 FAN
90, 60, 30
or 0 FAN
I SENS
I SENS
E SENS
A SENS
2 LOCK
2 LOCK
1 LOCK
3 BAND
2, 3, 4 or 5
BAND
NO BALC
NO BALC
15-50 BALC Select a Compressor Balance Point of 15°- 50°F
NO BALA
NO BALA
70-40 BALA Select a Auxiliary Heat Balance Point of 70°- 40° F
90-60 LIM
45-80 LIM
indoor remote sensor was connected.
®
Comments
(More information follows this table)
Disables Power Outage Lockout Delay
Enables Power Outage Lockout Delay
4, 3, 2 or 0 minutes
Select a Residual Cooling Fan Delay of 90, 60,
30 or 0 seconds.
Temperature is sensed from thermostat only.
Temperature is sensed from remote sensor only.
Temperature is combined with the thermostat and
t he remote sensor.
If locked – Complete lockout is enabled
If locked – Partial lockout is enabled (SpeedBar
still functional)
Select a Dead Band of 2°, 3°, 4° or 5˚ F
(1°, 2° or 3° C) for Auto Changeover mode.
Disables Balance Points
(-9°-10° C)
Disables Balance Points
(21°- 4° C)
Select a Heat Set Point Upper Limit of 90°-60° F (32°-10° C)
Select a Cool Set Point Lower Limit of 45°-80° F (7°-27° C)
10
is
®