6.1.2.2 BATTERY TEST

CAUTION!: CARRY OUT THE BATTERY TEST ONLY WHEN THE MACHINE IS
IN NORMAL MODE OPERATION.
The battery test allows the user to check battery connection quality and fuse condition. To
carry out the test press the F6 and the F3 keys together then press F6 to confirm, as specified
in diagram 1. The test lasts for a minute, during which the U.P.S. takes the necessary energy
to maintain its load from the battery. At the end of the test the result will appear under the
form of "Good Battery" or "Bad battery".
CAUTION!: PLEASE NOTE THAT SPECIALIZED TECHNICIANS MUST CARRY
OUT THE PROCEDURES DESCRIBED BELOW ONLY.
In the second case, that is to say "Bad batteries", you must check the fuses on the connecting
line between the U.P.S and the battery cabinet. To do so you must measure the direct voltage
on the battery fuse ends which are placed in the U.P.S and in the battery cabinet (see chapters
3.3 e 7.2) with a multimeter. If the fuses are not damaged, voltage measurement is next to
zero.
If the fuse check is positive, it means that the connected batteries are no longer suitable to
maintain the load if there is a power shortage.

6.1.3 FUNCTIONING MODE CONFIGURATION

This product gives you the possibility of configuring the functioning mode in order to modify its
use.

6.1.3.1 BATTERY CHARGE MODE

Press the F6 key and the starting key as specified in diagram 1a/b. These keys activate the
starting procedure which consists of the starting of the rectifier only (picture 6 point 2). This
makes it possible to charge the batteries through the terminal contacts C and D. This function
is very useful if the U.P.S. is not used for a long time and therefore needs complete battery
charge.

6.1.3.2 FORCING ON INVERTER MODE

To activate this function press the F6 key and the F2 key together as specified in diagram 1a/b.
This will mean that the system output will constantly be connected to the inverter, thus
excluding the emergency mains supply. While the system is starting up it provides output
energy only when the voltage level has reached set parameters. With this type of forcing it is
possible to start up the U.P.S. without the emergency mains supply.